6.7.1 Fault signal module
Via an internal relay, the fault signal module gives
access to a potential-free fault signal.
In addition to this fault signal output, the module has
four inputs for external signals for the forced-control
functions:
• Start/stop of pump.
• Max. curve duty.
• Min. curve duty (night-time duty).
• External analog control of head or speed from an
external 0-10 V signal transmitter.
Wiring diagrams of fault signal module:
Fig. 15
UPE 25-40, 25-40 A, 25-60, 25-60 A, 32-40 and
32-60 with MC 40/60
Fault signal
output
1
2
3
NCNO C
7
8
9
Stop
Note:
• If no external on/off switch is connected, the con-
nection across terminals 7 and 8 should be main-
tained.
• If the 0-10 V input is used (terminals 11 and 12),
there must be a connection across terminals
7 and 9 (the input for the min. curve must be
closed).
• All cables used must be heat-resistant up to at
least +85°C.
• All cables used must be installed in accordance
with EN 60 204-1.
12
Start/stop
Min. curve
(night-time duty)
Max. curve
Analog 0-10 V
input
10 11 12
DC 0-10 V
Min.
Max.
Fig. 16
UPE 25-80, 32-80, 40-80 and 50-80 with MC 80
Fault signal
output
1
2
3
NC NO C
7
8
9
Stop
• Wires connected to
- outputs 1 to 3,
- inputs 7 to 12 and
- supply terminals
must be separated from each other and
from the supply by reinforced insulation.
• All leads connected to a terminal block
must be tied up at the terminals.
Start/stop
Min. curve
(night-time duty)
Max. curve
Analog 0-10 V
input
10
11 12
DC 0-10 V
Min.
Max.