6.7.3 External fault signals
The expansion modules, type MC xx, have an output
from a potential-free changeover relay via terminals
2 and 3.
Functions of signal outputs:
Internal
Indicator Lights
relay
Contact
Fault
Opera-
position
tion
of termi-
(red)
(green)
nals
1, 2 and 3
Off
Off
1
NC NO C
Perma-
Off
nently
1
on
NC NO C
Flash-
Off
ing
1
NC NO C
Perma-
nently
Off
1 2
on
NC NO C
Perma-
Perma-
nently
nently
1 2
on
on
NC NO C
Perma-
Flash-
nently
ing
1 2
on
NC NO C
The fault signal output is activated when the pump
registers a fault. The fault signal relay is activated to-
gether with the red indicator light on the pump.
Resetting of fault indications:
A fault indication can be reset in one of the following
ways:
Briefly press "+" or "–" on the pump. This will not
influence the pump performance set.
Briefly switch off the electricity supply to the
pump.
By means of the R100, see section 7.4 R100.
The fault indication cannot be reset until the cause of
the fault has disappeared.
14
Description
The electricity
supply has been
2
3
switched off.
The pump is oper-
ating.
2
3
The pump has
been set to stop.
2
3
The pump has
stopped because
of a fault. Restart-
3
ing will be at-
tempted.
The pump is oper-
ating, but it has
been stopped be-
3
cause of a fault.
The pump has
been set to stop,
but it has been
3
stopped because
of a fault.

6.7.4 External forced control

The expansion modules MC xx and MB xx incorpo-
rate inputs for external signals for the forced-control
functions:
• Start/stop input (terminals 7 and 8).
• Max. curve duty (terminals 7 and 10).
• Min. curve duty (terminals 7 and 9).
During forced control, the light fields/indicator lights
on the pump will show which function is active.
Functional diagram: Start/stop input:
Start/stop
H
H
Functional diagram: Max. curve input:
The max. curve input is only active if the start/stop
input is closed.
Max. curve
H
H
Functional diagram: Min. curve input:
The min. curve input is only active if the start/stop in-
put is closed and the max. curve input is open.
Min. curve
H
H
Normal duty
Q
Stop
Q
Normal duty
Q
Max. curve
Q
Normal duty
Q
Min. curve
(night-time duty)
Q