4.2
Connecting the flowmeter sensor
4.2.1
Connecting the signal and magnet coil cables
The flowmeter sensor is connected to the transmitter via the signal / magnet coil cables (part
nos. D173D025U01 / D173D147U01). The coils of the flowmeter sensor are supplied with a
excitation voltage by the transmitter over terminals M1/M3. Connect the cables to the flowmeter
sensor according to the following drawing, using a screwdriver with proper size and width.
1
2
3
6
7
Fig. 22
1 red
2 blue
3 yellow
4 white
5 black
6 SE clamp
7 Signal cable
8 Grounding screw
9 Magnet coil cable

Terminal designation

1 + 2
1S, 2S
U+, U-
16
3A
3
M1 + M3
SE
D184B141U03
3A
16
1S
1
2
2S
3
3A
16
M3
M1
SE
SE
8
Connection
Wires for the measuring signal
Shielding for signal wires
Power supply for preamplifier via signal cable shielding
Cable for reference signal
Shielding for reference signal cable
Measuring ground (yellow)
Connections for magnetic field excitation (black)
Outer cable shield
FSM4000
1
4
U-
2
5
SE
3
6
6
9
7
G00553
1 red
2 blue
3 yellow
4 white
5 black
6 SE clamp
7 Signal cable
8 Grounding screw
9 Magnet coil cable
Electrical connection
3A
16
1
2
U+
3
3A
16
M3
M1
SE
8
EN - 19
4
5
6
9
G00554