Electrical connection
Observe the following items when routing cables:
The signal and magnet coil cable carries a voltage signal of only a few millivolts and
therefore must be routed the shortest distance possible. The maximum permissible signal
cable length is 50 m or 200 m, if the flowmeter sensor is equipped with a preamplifier.
Avoid routing the cable in the vicinity of electrical equipment or switching elements that can
create stray fields, switching pulses and induction. If this is not possible, run the
signal/magnet coil cable through a metal pipe and connect this to the station ground.
All leads must be shielded and connected to station ground.
Do not run the signal cable and the magnet coil cable over junction boxes or terminal blocks.
To shield against magnetic interspersion, the cable contains outer shielding that is attached
to the SE clamp.
Make sure during installation that the cable
is provided with a water trap (1). For vertical
installation, align the cable glands pointing
downward.
Important
For information about connecting or operating older models, refer to chapter 11 of the
operating instructions.