Siemens SIPART PS2 Betriebsanleitung Seite 64

Vorschau ausblenden Andere Handbücher für SIPART PS2:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Display
Parameter name
1. YFCT
[VALVE_TYPE]
2. YAGL
1)
[TRANSM_ANGLE]
3. YWAY
2)
[TRANSM_LENGTH]
4. INITA
[SELF_CALIB_COMMAND]
5. INITM
6.TSUP
[TRAVEL_RATE_UP]
7.TSDO
[TRAVEL_RATE_DOWN]
8. SFCT
[CHARACT_TYPE]
3)
9. SL0
up to
29. SL20
[TAB_VALUES]
30. DEBA
[DEADBAND]
31. YA
[TRAVEL_LIMIT_DOWN]
32. YE
[TRAVEL_LIMIT_UP]
33. YNRM
[Y_NORM]
34. YCDO
[FINAL_VALUE_
CUTOFF_LO]
35. YCUP
[FINAL_VALUE_
CUTOFF_HI]
36. BIN
4)
[BIN_IN_FUNCT]
37. AFCT
5)
[ALARM_FUNCT]
38. A1
[ALARM1]
39. A2
[ALARM2]
5)
40.
FCT
[FAULT_FUNCT]
41.
TIM
[DELAY_TIME]
42.
LIM
[TOLERANCE_BAND]
43.
STRK
[TOTAL_VALVE_
TRAVEL_LIMIT]
44.
DCHG
[LIMIT_DIRECTION_
CHANGE]
45.
ZERO
[LIMIT_ZERO_POINT]
46.
OPEN
[LIMIT_OPEN_VALUE]
47.
DEBA
[LIMIT_DEADBAND]
48. PRST
Function
Type of actuator
Rated angle of rotation of feedback
Set transmission ratio selector (7) appropriately
(see view of device)
Stroke range (optional setting)
When used, the value must correspond with
the set of the leverage ratio on the actuator
Driver pin must be set to the value of the actuator
travel or, if this value is not scaled, to the next
larger scale value.
Initialization (automatically)
Initialization (manually)
Setpoint ramp up
Setpoint ramp down
Setpoint function
Equal-percentage 1:25, 1:33, 1:50
Inverse equal-percentage 1:25, 1:33, 1:50
Freely adjustable
Setpoint turning point at 0%
5%, 10%, 15%
and so on up to
100%
Dead band of controller
Start of manipulated variable limiting
End of manipulated variable limiting
Standardization of
To mech. travel
manipulated variable
Value for tight closing, bottom
Value for tight closing, up
Function of BI
Only message
Block configuring
Block configuring and manual
Drive valve to position YE
Drive valve to position YA
Block movement
Without
Alarm function
A1=min. A2=max
A1=min. A2=min
A1=max. A2=max
Response threshold of alarm 1
Response threshold of alarm 2
Function of alarm output
Fault + not automatic
Fault + not automatic + BI
("+" means logical OR operation)
Monitoring time for fault message
"control deviation"
Response threshold for fault message
"control deviation"
Limit for stroke integral
Limit for direction change
Limit for end stop monitoring, bottom
Limit for end stop monitoring, top
Limit for dead band monitoring
Preset (factory setting)
"no" nothing activated
"Strt" start of factory setting after pressing key for 5 s
"oCAY" display following successful factory setting
Parameter values
turn (part-turn actuator)
WAY (linear actuator)
LWAY (linear actuator
without sine correction)
ncSt (part-turn actuator with NCS)
-ncSt (dito, inv. direction of action)
ncSL (linear actuator with NCS)
ncSLL (lin. act. with NCS and lever)
90°
33°
OFF
5 | 10 | 15 | 20
(short lever 33°)
25 | 30 | 35
(short lever 90°)
40 | 50 | 60 | 70 | 90 | 110 | 130
(long lever 90°)
no ###.# | Strt
|
| FINSH
no ###.# | Strt
|
| FINSH
Auto
0 up to 400
0 up to 400
Linear
Lin
1- 25
1 - 33
n1 - 25
n1 - 33
FrEE
0.0 up to 100.0
Auto
0.1 up to 10.0
0.0 up to 100.0
0.0 up to 100.0
MPOS
To flow
FLOW
OFF
0.0 up to 100.0
OFF
0.0 up to 100.0
OFF
None
on
bLoc1
bLoc2
uP
doWn
-doWn
StoP
OFF
0.0 up to 100.0
0.0 up to 100.0
on fault
Auto
0 up to 100
Auto
0.0 up to 100.0
1 up to 1.00E9
OFF
1 up to 1.00E9
OFF
0.0 up to 100.0
OFF
0.0 up to 100.0
OFF
0.0 up to 10.0
no
Strt
oCAY
Factory
Unit
setting
WAY
33°
Degrees
mm
OFF
no
no
s
0
s
0
Lin
1 - 50
n1 - 50
0.0
5.0
up to
100.0
%
Auto
0.0
%
%
100.0
%
MPOS
OFF
OFF
OFF
-on
-uP
-StoP
OFF
%
10.0
%
90.0
s
Auto
%
Auto
1.00E9
OFF
%
OFF
%
OFF
%
OFF
no
Customer
setting