Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens SIPART PS2 Betriebsanleitung Seite 60

Vorschau ausblenden Andere Handbücher für SIPART PS2:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Operating instruction
Fault description (symptoms)
CPU test blinks in the display of the
SIPART PS2 (ca. every 2 s)
Piezo valve(s) do not switch
Actuator cannot be moved in
manual or automatic mode, or only
in one direction
Piezo valve(s) do not switch (no
soft clicking can be heard when the
+ or -- keys are pressed in manual
mode)
Table 2
Fault description (symptoms)
Actuator does not move
Piezo valve(s) do not switch (al-
though a soft clicking can be
heard when the + or -- keys are
pressed in manual mode)
One piezo valve constantly
switches in stationary automatic
mode (constant setpoint) and in
manual mode
Table 3
58
Possible cause(s)
Water in the valve manifold (from
wet compressed air)
Dampness in the valve manifold
Screw between cover hood and the
valve manifold is not tight or the
hood is jammed
Dirt (swarf, particles) in the valve
manifold
Deposits on the contact(s) between
the electronics board and the valve
manifold can occur from abrasion
through continuous stresses from
strong vibrations
Possible cause(s)
Compressed air < 1.4 bar
Restrictor(s) closed down
(screw(s) at the right end stop)
Dirt in the valve manifold
Pneumatic leak in the positioner,
actuator system, start leak test in
RUN 3 (Initialization) !!!
Dirt in the valve manifold (see
above)
Corrective actions
At the early stages the fault can be
corrected by subsequent operation
with dry air (when necessary, in a
with dry air (when necessary, in a
temperature cupboard at 50 to
70 °C)
Otherwise: repair, see page 60
Tighten screw, or release cause of
jamming when necessary
Repair, see page 60 or new device
with integrated fine filter which can
be replaced and cleaned
Clean all contact surfaces with alco-
hol: when necessary bend the valve
manifold contact springs back into
place
Corrective actions
Set inlet air pressure to > 1.4 bar
Open restrictor screw(s) (see leaf-
let, Figure "View of device (6) on
page 61") by turning to the left
Repair, see page 60 or new de-
vice with integrated fine filter
which can be replaced and
cleaned
Fix leak in the actuator and/or
supply line
If the actuator and supply line are
intact: repair, see page 60
See above
SIPART PS2 EEx d FF
A5E00351419--01

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis