Operating instruction
This parameter only has to be set if you wish to have the determined total stroke displayed in mm at the end
of the initialization phase. To do this, select the same value in the display that you have set with the driver
pin on the lever scale, or the next highest value for intermediate settings.
5.
Move to the following display by pressing the mode key
Display:
6.
Start initialization by pressing the increment key for more than 5 s.
Display:
7.
After 5 s, the display changes to:
Display:
(The display of the potentiometer setting is shown here and in the following as an example only).
Drive the actuator with the increment (+) and decrement (--) keys to the position that you wish to define as
the first of the two end positions. Then press the mode key
as end position 1 and will switch to the next step.
.
NOTE
If the message RANGE appears in the lower line, the selected end position is outside the
permissible measuring range. There are several options to correct this error:
S Adjust the external friction clutch until "OK" appears and then press the operating mode button
again, or
S Drive to another end position with the increment and decrement keys, or
S Interrupt the initialization by pressing the mode key. Then you have to switch to P--Manual mode
and correct the travel and the position measurement according to step 1.
8.
When step 7 has been completed successfully, the following display appears:
Display:
Now drive the actuator with the increment (+) and decrement (--) keys to the position that you wish to define
as the second end position. Then press the mode key
the end position 2.
.
NOTE
If the message RANGE appears in the lower line, the selected end position is outside the permitted
measuring range or the measuring span is too small. There several options to correct this error:
S Drive to another end position with the increment and decrement keys, or
S Interrupt the initialization by pressing the mode key. Then you have to switch to P--Manual mode
and correct the travel and the position measurement according to step 1.