1
Preface
Please read this instruction manual
carefully before installation and start-up.
Please observe all warnings and
advices, both for your own safety and
for general plant safety. If the device is
not used in accordance with this
instruction manual, then the intended
protection can be impaired.
2
Safety instructions and
warnings
Please use the device only if its
technical condition is perfect. It should
be used only for its intended purpose.
Please bear in mind safety aspects and
potential dangers and adhere to these
operating instructions
2.1
Use according to the intended
purpose
The CAN display shows CANopen process values
using a 6-digit 7-segment display. Parameterizing is
carried out via the CANopen bus. The display
supports the transmission according to the CAN
specification 2.0A/2.0B up to 1 MBaud max.
Addressing 16 different addresses is possible using
the rotary coding selector switch on the back side
of the device.
The application area for this device lies in industrial
processes and controls, in the fields of
manufacturing lines for the metal, wood, plastics,
paper, glass, textile and other like industries. Over-
voltages at the screw terminals of the device must
be kept within the limits of over-voltage category II.
The device shall only be operated when properly
mounted in a panel and in compliance with the
chapter "Technical data". The device requires, for a
correct operation, an external protection by means
of a fuse. The device is not suitable for use in
hazardous areas and for areas excluded from
standard EN 61010 Part 1.
If the device is used to monitor machines or
processes in which, in the event of a failure of the
device or an error made by the operator, there
might be the risk of damaging the machine or
causing an accident to the operators, then it is your
responsibility to take the appropriate safety
measures.
Use for any purpose over and beyond this will be
deemed as not in accordance with its intended
purpose.
www.kuebler.com
2.2
Front panel mount
Mount the device away from heat
sources and avoid direct contact
with corrosive liquids, hot steam or
similar.
CAUTION
Mounting instructions
1.
Remove the mounting clip from the device.
2.
Insert the device from the front into the panel
cut-out, ensuring the front-panel gasket is
correctly seated.
3.
Slide the fixing clip from the rear onto the
housing, until the spring clamps are under
tension and the upper and lower latching lugs
have snapped into place.
2.3
Electrical installation
This device must be disconnected
from the power supply and from the
CAN bus, before any installation or
maintenance work is carried out.
WARNING
Installation or maintenance work
shall only be carried out by qualified
personnel.
Advice on noise immunity
All connections are protected against external
sources of interference. The installation location
should be chosen so that inductive or capacitive
interference does not affect the device or its
connecting lines! Interference (e.g. from switch-
mode power supplies, motors, clocked controllers
or contactors) can be reduced by means of
appropriate cable routing and wiring.
Measures to be taken:
Use only shielded cable for signal and control lines.
Connect the cable shield at both ends. Braid cross
section of the cables: min. 0.14 mm².
The shield connection to the equipotential bonding
should be as short as possible and with a contact
area as large as possible (low impedance).
Only connect the shields to the control panel, if the
latter is also earthed.
Install the device as far away as possible from
noise-containing cables.
Avoid routing the cables parallel to power lines.
Cables and their insulation should be in accordance
with the intended temperature, voltage and power
ranges.