Operation of the Unit
Reaction to limit switch
GB
GB
Reaction to external fault
GB- 26
This parameter determines the reaction of the drive, to terminal X2A.14
(F) and/or X2A.15 (R). These terminals are programmed as software limit
switches. The reaction of the drive is shown in the table below.
CP.35 Display Reaction
0
E.PRx Immediate disabling of modulation
1
A.PRx Quick stopping / disabling of
modulation after reaching speed 0
2
A.PRx Quick stopping/holding toruqe at speed 0
3
A.PRx Immediate disabling of modulation
4
A.PRx Quick stopping / disabling of
modulation after reaching speed 0
5
A.PRx Quick stopping/holding toruqe at speed 0
6
keine No effect on the drive;
! Fault is ignored !
Adjustment range:
Resolution:
Factory setting:
With the external error monitoring external units can take direct influence
on the drive. This parameter determines the response of the drive to a
signal at terminal X2A.12 (I3) according to following table.
CP.36 Display Reaction
0
E. EF Immediate disabling of modulation
1
A. EF Quick stopping / disabling of
modulation after reaching speed 0
2
A. EF Quick stopping/holding toruqe at speed 0
3
A. EF Immediate disabling of modulation
4
A. EF Quick stopping / disabling of
modulation after reaching speed 0
5
A. EF Quick stopping/holding toruqe at speed 0
6
keine No effect on the drive;
! Fault is ignored !
Adjustment range:
Resolution:
Factory setting:
Restart
Remove fault;
Actuate reset
Automatic reset,
if the fault is no
longer
present
- inapplicable -
0...6
1
6
Restart
Remove fault;
Actuate reset
Automatic reset,
if the fault is no
longer
present
- inapplicable -
0...6
1
0