Herunterladen Inhalt Inhalt Diese Seite drucken

Parker 650 series Bedienungsanleitung Seite 69

Vorschau ausblenden Andere Handbücher für 650 series:
Inhaltsverzeichnis

Werbung

Application 4: Raise/Lower Trim
This Application mimics the operation of a motorised potentiometer. Digital inputs allow the setpoint to be increased and
decreased between limits. The limits and ramp rate can be set using the keypad.
The Application is sometimes referred to as Motorised Potentiometer.
SINGLE
WIRE
STARTING
User Relay
Control
Terminal
10
DIN4/DOUT2
RESET
9
DIN3
LOWER INPUT
8
DIN2
RAISE INPUT
7
DIN1
RUN FORWARD
6
+24V
24V
5
AOUT
RAMP OUTPUT
4
+10V REF
+10V REF
3
AIN2
Not Used
2
AIN1
Not Used
1
0V
0V
RL1A
DOUT3 (relay)
RELAY SOURCE
RL1B
Applications
24V = reset Raise/Lower
24V = lower input
24V = raise input
24V = run forward
= 1
DEMAND (0V = 0%, 10V = 100%)
= 1
HEALTH i.e. 0V = not healthy