Programming Your Application
SKIP FREQUENCY
1
SKIP FREQUENCY
BAND 1
SKIP FREQUENCY
2
SKIP FREQUENCY
BAND 2
AUTO RESTART
ATTEMPTS
AUTO RESTART
DELAY
AUTO RESTART
TRIGGERS
AUTO RESTART
TRIGGERS+
LOCAL MIN
SPEED
F
ENABLED KEYS
F
Parameter Setting RUN
0000
0010
0020
0030
0040
0050
0060
0070
6901
0080
0090
00A0
00B0
00C0
00D0
00E0
00F0
6911
6511
6521
APPLICATION
LOCK
F
DETAILED MENUS Selects Full menu detail when TRUE. The additional
This parameter contains the centre frequency of
skip band 1 in Hz
The width of skip band 1 in Hz
This parameter contains the centre frequency of
skip band 2 in Hz
The width of skip band 2 in Hz
Determines the number of restarts that will be
permitted before requiring an external fault reset
Determines the delay between restart attempts for
a trip included in AUTO RESTART TRIGGERS and
AUTO RESTART TRIGGERS+. The delay is
measured from all error conditions clearing
Allows Auto Restart to be enabled for a selection of
trip conditions.
Refer to Chapter 6: "Trips and Fault Finding" -
Hexadecimal Representation of Trips
Allows Auto Restart to be enabled for a selection of
trip conditions.
Refer to Chapter 6: "Trips and Fault Finding" -
Hexadecimal Representation of Trips
The magnitude of the minimum setpoint that will
be used when running in Local Mode.
The following keys on the 6901 keypad can be
enabled or disabled separately. The combination
produces the parameter setting as in the table
below. The default of FFFF enables all keys.
L/R
JOG
-
-
-
-
-
-
-
-
ENABLED
-
-
ENABLED
-
ENABLED
-
-
ENABLED
-
-
ENABLED
ENABLED
-
ENABLED
ENABLED
ENABLED
-
-
ENABLED
-
-
ENABLED
-
ENABLED
ENABLED
-
ENABLED
ENABLED
ENABLED
-
ENABLED
ENABLED
-
ENABLED
ENABLED
ENABLED
ENABLED
ENABLED
ENABLED
When using the standard 6511 and 6521 keypad,
disabling the DIR key prevents the local setpoint
going negative (for reverse). Similarly, disabling
the L/R key prevents the drive being changed from
Local to Remote, or Remote to Local modes.
Setting this parameter to TRUE prevents editing of
parameter
P
1.
Set this parameter to FALSE to edit parameter
parameters in the Full menus are indicated in this
table by
F
0.0 to 240.0 Hz
0.0 to 60.0 Hz
0.0 to 240.0 Hz
0.0 to 60.0 Hz
0 to 10
0.0 to 600.0 s
0x0000 to 0xFFFF
0x0000 to 0xFFFF
0.0 to 100.0 %
0000 to FFFF
DIR
-
ENABLED
-
ENABLED
-
ENABLED
-
ENABLED
-
ENABLED
-
ENABLED
-
ENABLED
-
ENABLED
0=FALSE
1=TRUE
P
1.
0=FALSE
1=TRUE
0.0
0.0
0.0
0.0
0
10.0
0x0000
0x0000
0.0 %
FFFF
0
0
650 Series AC Drive