Herunterladen Inhalt Inhalt Diese Seite drucken

Parker 650 series Bedienungsanleitung Seite 27

Vorschau ausblenden Andere Handbücher für 650 series:
Inhaltsverzeichnis

Werbung

MMI Parameters Table
Display
Parameter
MOTOR
CURRENT
M
BASE
FREQUENCY
M
JOG SETPOINT
RUN STOP MODE RAMPED : The motor speed is reduced to zero at a
V/F SHAPE
NORMAL DUTY
650 Series AC Drive
Description
This parameter contains the motor nameplate full-
load line current
The output frequency at which maximum voltage is
reached. The default can be either 50 or 60Hz.
Speed the 650 will run at if the Jog input is high,
as a percentage of the MAX SPEED parameter
rate set by DECEL TIME (
P
5). A 2 second DC pulse
is applied at end of ramp
COAST : The motor is allowed to freewheel to a
standstill
DC INJECTION : On a stop command, the motor
volts are rapidly reduced at constant frequency to
deflux the motor. A low frequency braking current
is then applied until the motor speed is almost
zero. This is followed by a timed DC pulse to hold
the motor shaft.
LINEAR LAW: This gives a constant flux
characteristic up to the BASE FREQUENCY
FAN LAW: This gives a quadratic flux characteristic
up to the BASE FREQUENCY. This matches the
load requirement for fan and most pump
applications
Refer to
P
12
OUTPUT VOLTS
100%
LINEAR
QUADRATIC LAW
f B
= BASE FREQUENCY
% OF RATED MOTOR CURRENT
100% overload for 30s (Heavy Duty)
150%
127.5%
105%
100%
30
60
FALSE - HEAVY DUTY: Inverse time allows 150%
overload for 30s, then ramps back the current limit
to 105% over a 10s period. At a lower load, the
overload area remains the same, e.g. at 127.5%
load for 60s - after 60s has expired, the output of
the inverse time function is ramped back over a
10s period from 150% as before.
TRUE - NORMAL DUTY: current limit is set to
110% motor current, inverse time delay is set to
30s
When
P
11 is changed from FAN LAW to LINEAR
LAW,
P
12 is set to 0 (HEAVY DUTY)
When
P
11 is changed from LINEAR LAW to FAN
LAW,
P
12 is set to 1 (NORMAL DUTY)
P
12 can be changed independently
Programming Your Application
Range
0.01 to 999.99A
7.5 to 240Hz
-100.0 to 100.0%
0=RAMPED
1=COAST
2=DC INJECTION
0=LINEAR LAW
1=FAN LAW
CONSTANT
POWER RANGE
FREQUENCY
f B
0=FALSE
1=TRUE
TIME (s)
6-2
Default
product
code
dependent
product
code
dependent
10.0%
0
0
0
NORMAL DUTY was
previously referred to
as Quadratic Torque
in past Drives'
manuals.

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ac driveFrame 1Frame 2: frame 3

Inhaltsverzeichnis