Parker 650 series Bedienungsanleitung Seite 31

Vorschau ausblenden Andere Handbücher für 650 series:
Inhaltsverzeichnis

Werbung

MMI Parameters Table
Display
Parameter
REMOTE COMMS
SEL
F
COMMS
TIMEOUT
F
COMMS
ADDRESS
F
BAUD RATE
F
PARITY
F
REPLY DELAY ms
OP PORT
PROTOCOL
F
P3 PORT
PROTOCOL
F
JOG ACCEL TIME As
JOG DECEL TIME As
RAMP TYPE
S RAMP JERK
S RAMP
CONTINUOUS
MIN SPEED
MODE
F
650 Series AC Drive
Description
SET::SERL Menu
Selects the type of remote communications mode:
0 : FALSE, and in REMOTE mode then control is
from the terminals.
1 : TRUE, and in REMOTE mode then control is
from the communications.
Se
ts the maximum time allowed between
refreshing the COMMS COMMAND parameter.
The drive will trip if this time is exceeded. Set the
time to 0.00 seconds to disable this feature.
The drives identity address.
Note: if set to 0, it will only respond to broadcast
messages.
Selects the Baud Rate for the MODBUS protocol.
Selects the Parity for the MODBUS protocol.
The time in milliseconds between the drive
receiving the complete request from the
communications master (PLC/PC) and replying to
this request.
Selects the protocol to be used by the keypad port
on the front of the drive. When EIBISYNC ASCII is
selected, BAUD RATE is 19200 and PARITY is
EVEN. FIELDBUS is reserved for future use.
Selects the protocol to be used by the RS232
programming port on the drive's control board.
When EIBISYNC ASCII is selected, BAUD RATE is
19200 and PARITY is EVEN. FIELDBUS is reserved
for future use.
SET::SETP Menu
P
4, for Jog
P
5, for Jog
Selects the ramp type
Rate of change of acceleration of the curve in units
per second³
When TRUE and the S ramp is selected, forces a
smooth transition if the speed setpoint is changed
when ramping. The curve is controlled by the S
RAMP JERK parameter. When FALSE, there is an
immediate transition from the old curve to the new
curve
Selects a mode to determine how the drive will
follow a reference: Proportional : minimum limit,
Linear : between minimum and maximum.
Programming Your Application
Range
0=FALSE
1=TRUE
0.0 to 600.0s
0 to 255
0 : 1200
1 : 2400
2 : 4800
3 : 7200
4 : 9600
5 : 14400
6 : 19200
7 : 38400
8 : 57600
0= NONE
1= ODD
2= EVEN
0 to 200
0= AUTOMATIC
1= KEYPAD
2=EIBISYNC ASCII
3= MODBUS
4= FIELDBUS
As
0.0 to 3000.0s
0.0 to 3000.0s
0=LINEAR
1=S
0.01 to 100.00 s3
0=FALSE
1=TRUE
0=PROP.W/MIN.
1=LINEAR (used by
the 601 product)
6-6
Default
0
0.0s
0
4
0
5
0
S
SE07
0
1.0
1.0
0
10.00
1
0