WARNING
Risk from electrical voltage!
»
Electrical connection only by a trained electrician or trained and instructed qualifi ed personnel!
»
Electrical connection in harmony with the valid directives.
»
Pay attention to the 5 rules of electrical engineering:
clear (all-pole separation of an electrical system from live parts),
secure against switching on again
establish freedom from voltage,
earth and short-circuit,
cover or fence off neighbouring live parts.
CARE
Property damage from overheating of the motor
The motor can overheat and be destroyed if the thermo-contacts have not been connected.
»
Always connect the thermo-contacts to a motor-protection device!
8.5.1
Electrical connection of the fan
 Remove the circuit diagram of the motor from the terminal block.
 Connect the electrical lines on the basis of the instructions for the motor.
8.5.2
Electrical connection of PRF-EX fans
Secure 3-phased motors
 Avoiding two-phased runs:
For 3-phased motors, use an effective motor protection, we recommend an all-pole C automatic
cut-out.
Connect temperature monitor
 If a temperature monitor is used, it must be connected to a triggering device and/or a motor pro-
tection device.
9

Commissioning

9.1

Safety information

HAZARD
Hazard from electrical voltage.
»
ICommissioning may only be carried out by trained and qualifi ed personnel.
»
Electrical connection in harmony with the valid directives.
Comply with fundamental information in the commissioning of the EX fan:
BGR 104 (explosion protection rules of the employers' insurance schemes)
BGR 132 (avoidance of risk of ignition as a result of electrostatic charges).
Fan types PRF and PRF EX - 10.2013