Supply Voltage Interruption

8.1 Reaction when Supply Voltage is Restored
When the supply voltage is interrupted, the Presence Detector reacts as follows:
a. Interruption ≤ 200 ms
- No change in the output state
b.Interruption > 1 s
"Time" potentiometer is set to:
- between 10 s and 1 min.:
Irrespective of the brightness measured, the lighting will be switched on for one
minute. The Presence Detector then reverts to its normal mode of operation.
- a value ≥ 1 min.:
Irrespective of the brightness measured, the lighting will be switched on for one
minute in accordance with the switch-off delay set on the "Lux" potentiometer. The
Presence Detector then reverts to its normal mode of operation.
- short-time impulse
Irrespective of the brightness measured and the brightness limit value selected, the
lighting will be switched as follows:
GB