Level malfunction
Duo Pumpe 1/2
Single Pump Aqualift F
• "Pump Off" float switch which does not activate.
In the case that the "Pump Off" float switch does not shut off,
the alarm warning will be activated when the wastewater
level rises above the "Pump On" level. The pump will turn off
when the wastewater level falls below the "Pump On" level.
• "Pump On" float switch which does not activate.
The alarm will activate and the pump will start when the wa-
stewater rises above the "Alarm On" level. Pump will turn off
when the level falls below the "Pump On" level.
• "Pump On" float switch which is stuck in the "On" position.
A warning will be displayed after the wastewater falls below
the "Pump Off" level. The pump remains in activation.
• "Alarm" float switch is stuck in the "On" position.
A warning will be displayed after the wastewater level has fal-
len below the "Pump On" level – the warning will be a conti-
nuous (non-stop) alarm warning. The alarm can be acknow-
ledged by pressing the Alarm button. The warning relay will
remain activated until the problem has been cleared / fixed.
The pump continues to run. A level malfunction warning
occurs .
Double Pump Aqualift F
• "Pump Off" float switch which does not activate.
Malfunction warning occurs when the Pump 1 On level ex-
ceeded. Both pumps activate only when the wastewater level
exceeds the Pump 2 On level and turn off when the level falls
below the Pump 1 On level
• "Pump On" float switch which does not activate.
Malfunction warning occurs after wastewater level falls
below the Pump Off level. The pumps remain in operation. A
level malfunction warning occurs
• "Pump 2 On" float switch which does not activate.
An alarm will activate after the wastewater level has fallen
below above the "Pump Off" level. Both pumps will continue
to run. A level malfunction warning occurs
8. Problems and Solutions
• Level malfunction
A float switches has activated without one of the float switches below activating first
(incorrect order of float switch activation)
--> Check all float switch cables to make sure they are not tangled or wrapped up.
Make sure all float switches can move freely
--> Check float switches for proper operation
71
• Constantly closed "Pump 1 On" level switch.
An alarm will activate after the wastewater level has fallen
below the "Pumps Off" level. Both pumps will continue to run.
A level malfunction warning occurs.
• Constantly closed "Pump 2 On" level switch.
An alarm will activate after the wastewater level has fallen
below the "Pumps Off" level. Both pumps will continue to run.
A level malfunction warning occurs.
• Constantly closed "Alarm" level switch.
Malfunction warning occurs after the wastewater level falls
below the 'Pump On' level. A continuous alarm sounds. The
alarm can be acknowledged by pressing the Alarm button.
The warning relay will remain activated until the problem has
been cleared / fixed. The pump continues to run. A level mal-
function warning occurs

8.3 Disturbances / Internal controls

The control unit continuously monitors motor temperature,
the motor protection switch and the rotation / phase of the
motors. In the case of a disturbance the pump will either be
shut off or prevented from starting. This will result in a corre-
sponding alarm and the lighting of an LED.
8.3.1 Phase / Rotation Monitoring
In the case that L2 and / or L3 fail, the "Phase/Drehfeld" LED
will continuously light and the "Störung" relay will activate.
Since the control of L1 is still active, the failure of L1 will not
be displayed. In the case that L1 fails the installed warning
device will sound as long a battery has been installed in the
control unit. In the case that the rotation is incorrect, the
"Phase / Drehfeld" LED will blink.
In the operational mode "Hand" it is possible to run the pump
with the incorrect rotation – in all other operational modes the
control unit will block the functioning of the motor in the case
that the rotation is incorrect.