5.6 Controls

Checking the motor protection switches
The motor protection switch must be set for the ap-
propriate rated current of the pumps – as described
in Section 3 of this manual.
5.8 Control unit configuration (Models Jan 2010 and newer)
The DIP switches are in the upper right portion of the control unit and have been set at the factory. Due to the explo-
sion proof rating antiblocking mechanism has been switched off (switch 4) and must not be activated!
1.
2.
1
2
3 4
3.
4.
5.9 Control unit configuration (Models December 2009 and older)
The control unit configuration is set at the factory using switches S601 to S 604 which are between the levels switch connec-
tion jacks and the thermal protection inputs. These should be checked using the table below to make sure they are correct
– the proper settings are marked in grey.
– The four DIP switches (switch S604) are set at the factory and should not be changed.
Models December
2009 and older
S604 / 1
S604 / 2
S604 / 3
S604 / 4
5. Electrical connections
Switch: Sensor
• Switch 1 up: Level measuring with float switches
• Switch 1 down: Level measuring with pressure switch
Switch: Level heights
• Switch 2 up: Pumpstation (underground pumpstation)
• Switch 2 down: Lifting station (floor mounted or dry mount inside chamber)
Switch: This switch for customer service partners only
Switch: Anti blocking function
• Switch 4 up: anti blocking off
• Switch 4 down: anti blocking on
ON
(lifting station)
running time control
Submersible pump
without OFF float switch
Rotation / Phase controlled
On
Anti blocking function
On
61
5.7 Completion of electrical work
After all electrical connection work has been completed in the
control unit, the control unit cover must be closed and pro-
perly secured. In order to eliminate odour nuisances in the
area where the control unit is installed, the conduit pipe to the
control unit should be sealed with a special gaskets or simp-
ly with insulation foam.
(submersible pump station)
with OFF float switch
Rotation / Phase controlled
Anti blocking function
OFF
level controlled
Submersible pump
Off
Off