Manual setting of upper / lower endpoint with a cord circuit setting unit or
with an external switch
1.
2.
SET
3.
ON
SET
+
4.
SET
5.
SET
6.
7.
Symbols and actions when connecting a cord circuit setting unit (20)
or
when connecting an external switch.
Switch off the mains power.
or
OFF
If a cord circuit setting unit (20) is being used, then the rocker switch must be positioned to the centre position.
Press and hold the SET button or the external switch.
or
Additionally switch on the mains power.
or
+
After approx. 6 seconds the tubular motor starts and the awning moves up or down.
ON
Release the SET button as soon as the awning have reached the desired position.
or
The motor stops and the first end point is stored.
You can correct the end point in small steps by briefly pressing the SET button.
or
IMPORTANT
In the event that a malfunction occurs during configuration, e.g. in the event that the tubular motor only runs for a single rotation even when
the SET button is pressed, it is unlikely that the tubular motor is faulty. Possibly the adapter (8) has slipped off of the motor head.
Check and, if necessary, correct the positioning of the adapter (8), (see page 46).
NOTE
The end points are maintained permanently even in the event of power failure.
Switch off the mains power again.
or
OFF
Repeat points 2. to 5. for the second end point.
IMPORTANT
◆ The external switch lead (h) must be connected to neutral conductor (f) after configuration of the end points.
◆ If the end points have been set manually, the "fabric tensioning" function will be deactivated.