Fuses and cable cross−sections
Type
E82MV302_4B
E82MV402_4B
E82MV552_4B
E82MV752_4B
1)
Use UL−approved cables, fuses and fuse holders only.
UL fuse: 500 ... 600 V voltage, tripping characteristic "H", "K5" or "CC"
2)
Universal−current sensitive earth−leakage circuit breaker
Observe all national and regional regulations!
When using earth−leakage circuit breakers, observe the following:
l
Earth−leakage circuit breakers must only be installed between mains supply and controller.
l
Earth−leakage circuit breakers can trip incorrectly due to
– capacitive compensation currents of the cable shields during operation (especially with long,
shielded motor cables),
– simultaneous connection of several controllers to the mains supply,
– the use of additional RFI filters.
3.4.2

Relay connection (only for device versions 001, 151)

Fig. 34
Relay connection
Function
X1/K11
NC contact relay output
X1/K12
Relay middle contact
X1/K14
NO contact relay output
PES
HF shield termination by PE connection with a surface as large as possible
)
L
efesotomasyon.com - Lenze
Mains
Installation to EN 60204−1
Fuse
M16 A
3/PE AC
M20 A
320 ... 550 V;
M25 A
45 ... 65 Hz
M32 A
Relay position set
Note!
For switching the control signals use shielded cables and establish an HF shield
l
termination by PE connection.
For mains potential switching unshielded cables are sufficient.
l
With inductive or capacitive loads a corresponding protective circuit is required in
l
order to protect the relay contacts!
l
The service life of the relay depends on the type of load (ohmic, inductive or
capacitive) and the value of the switching capacity.
The output message can be changed under C0008 or C0415/1.
l
EDK82MV752 DE/EN/FR 6.0
Installation
Electrical connection
E.l.c.b.
L1, L2, L3, PE
2
[mm
]
B16 A
2.5
B20 A
4.0
B25 A
4.0
B32 A
6.0
Message
(Lenze setting)
open
TRIP
closed
TRIP
1)
Installation to UL
E.l.c.b.
Fuse
L1, L2, L3, PE
[AWG]
15 A
14
20 A
12
³ 300 mA
25 A
10
35 A
8
8200mot410
Technical data
AC 250 V/3 A
DC 24 V/2 A ... DC 240 V/0.22 A
2)
83