Fault detection and elimination

Malfunction of the drive

5

Troubleshooting and fault elimination

5.1
Malfunction of the drive
Fault
Cause
Motor does not rotate
DC−bus voltage too low
(Red LED is blinking every 0.4 s;
keypad display
Controller inhibited
(Green LED is blinking, keypad display:
Automatic start inhibited (C0142 = 0 or 2)
DC injection brake (DCB) active
Mechanical motor brake is not released
Quick stop (QSP) active (keypad display:
Setpoint = 0
JOG setpoint activated and JOG frequency = 0
Active fault
Wrong parameter set active
Operating mode C0014 = −4−, −5−, but no motor parameter identification
executed
Under C0410 several functions which exclude each other, are assigned
to the same signal source.
Use of internal voltage source X3/20 for function modules Standard I/O,
INTERBUS, PROFIBUS−DP or LECOM−B (RS485):
Jumper between X3/7 and X3/39 is missing
Motor does not rotate
Defective motor cable
smoothly
Maximum current set too low (C0022, C0023)
Motor underexcited or overexcited
C0084, C0087, C0088, C0089, C0090, C0091 and/or C0092 are not
adapted to the motor data
Current consumption of
Setting of C0016 too high
motor too high
Setting of C0015 too low
C0084, C0087, C0088, C0089, C0090, C0091 and/or C0092 are not
adapted to the motor data
Motor rotates, setpoints are
With the function
0"
Motor parameter
Motor too small compared with rated device power
identification stops with
DC injection brake active via terminal
error LP1
Unacceptable drive response
various
with vector control
Torque dip in the field
various
weakening range
Stalling of the motor when
operating in the field
weakening range
102
efesotomasyon.com - Lenze
LU
)
c
)
c
)
j
of the keypad a setpoint has been selected.
EDK82MV752 DE/EN/FR 6.0
Remedy
Check mains voltage
Remove the controller inhibit, controller inhibit can be set
through several sources
LOW−HIGH edge at X3/28
If necessary, correct start condition (C0142)
Deactivate DC injection brake
Manual or electrical release of mechanical motor brake
Remove quick stop
Select setpoint
Select JOG setpoint (C0037 ... C0039)
Eliminate fault
Change to correct parameter set via terminal
Motor parameter identification (C0148)
Correct configuration in C0410
Jumper terminals
Check motor cable
Adapt settings to the application
Check parameter setting (C0015, C0016, C0014)
Manual adaptation or identification of motor parameters
(C0148)
Correct setting
Correct setting
Manual adaptation or identification of motor parameters
(C0148)
Set the setpoint to "0" via C0140 = 0
Optimise vector control (¶ 95)
Contact Lenze