Fault detection and elimination

Fault messages

5.3
Fault messages
5.3.1
Fault messages on the keypad or in the parameter setting program Global
Drive Control
1)
Keypad
PC
Fault
0
No fault
noer
71
System failure
ccr
a
61
Communication error on AIF
ce0
a
(configurable in C0126)
62
Communication error on
ce1
a
CAN−IN1 with sync control
63
Communication error on
ce2
a
CAN−IN2
64
Communication error on
ce3
a
CAN−IN1 in case of event or
time control
65
BUS−OFF
ce4
a
(many communication errors
occurred)
66
CAN time−out
ce5
a
(configurable in C0126)
67
System bus (CAN) function
ce6
a
module on FIF has the
"Warning" or "BUS−OFF"
status
(configurable in C0126)
68
Communication error in case
ce7
a
of remote parameterisation via
the system bus (C0370)
(configurable in C0126)
91
External fault (TRIP−SET)
EEr
a
Communication abort between
ErP0
keypad and standard device
...
ErP19
a
95
Fan failure
FAn1
a
(only 8200 motec 3 ... 7.5 kW)
TRIP or warning configurable
FAn1
in C0608
105
Internal fault
H05
a
140
Faulty parameter identification
id1
a
104
efesotomasyon.com - Lenze
Cause
Strong interference injections on the control cables Shield control cable
Earth loops in the wiring
Faulty transmission of control commands via AIF
CAN−IN1 object receives faulty data or
communication is interrupted
CAN−IN2 object receives faulty data or
communication is interrupted
CAN−IN1 object receives faulty data or
communication is interrupted
Controller has received to many faulty telegrams
via the system bus and has been disconnected
from the bus
In case of remote parameterisation via the system
bus (C0370):
Slave does not respond. Communication
monitoring time has been exceeded
When operating with Application I/O:
Parameter set change−over has been
parameterised incorrectly
When operating with module on FIF:
Internal error
CAN controller signals "Warning" or "BUS−OFF"
status
Node does not respond or is not available
When operating with Application I/O:
Parameter set change−over has been
parameterised incorrectly
A digital signal assigned to the TRIP−set function is
activated
Various
Fan is defective
Fan is not connected
Motor is not connected
EDK82MV752 DE/EN/FR 6.0
Remedy
Insert the communication module properly into the
diagnosis terminal
·
Check plug connection of bus module ó FIF
·
Check sender
·
Increase monitoring time in C0357/1, if necessary
·
Check plug connection of bus module ó FIF
·
Check sender
·
Increase monitoring time in C0357/2, if necessary
·
Check plug connection of bus module ó FIF
·
Check sender
·
Increase monitoring time in C0357/3, if necessary
·
Check whether bus termination is available
·
Check shielding of the cables
·
Check PE connection
·
Check bus load, reduce the baud rate, if necessary
·
Check wiring of the system bus
·
Check system bus configuration
In all parameter sets, the "change over parameter set"
signal (C0410/13, C0410/14) must be connected with the
same source
Contact Lenze
·
Check whether bus termination is available
·
Check shielding of the cables
·
Check PE connection
·
Check bus load, reduce the baud rate, if necessary
·
Check whether bus termination is available
·
Check shielding of the cables
·
Check PE connection
·
Check bus load, reduce the baud rate, if necessary
In all parameter sets, the "change over parameter set"
signal (C0410/13, C0410/14) must be connected with the
same source
Check external encoder
Contact Lenze
Replace fan
Connect fan
Check wiring
Contact Lenze