Wiring according to EMC (installation of a CE−typical drive system)
Conditions for trouble−free operation:
l
Except for the mains cable, use shielded cables only.
l
The shield must be carefully connected to PE (see below).
l
Connect motor and mains PE conductors to separate PE terminals.
A
B
X1
G
D
X2
F
F
Fig. 32
Wiring according to EMC
0
Relay connecting cable
1
Mains cables L1, L2, L3, PE (loop through 2 cables to the mains)
2
PE connection for mains cables
3
Shielded control cables; fix the shield tightly to the sheet with the
cable tie
4
PE connection for motor cable
5
Shielded control cables
6
Isolated terminal (e.g. star point for star connected motor)
X1
Terminal strip − mains connection
X2
Terminal strip − motor connection
PES HF shield connection by connecting the shield with a surface as
large as possible to PE
L
efesotomasyon.com - Lenze
Shield connection
1. Prepare the cable
B
2. Insert the cable tie
C
3. Lay the cable into the
cable tie and tighten it.
The shield must be
I
tightly connected to
the shield sheet.
F
82mot395
EDK82MV752 DE/EN/FR 6.0
Installation
Motor mounting
J
I
7
FIF support
8
Bus−I/O function module in slot 1
9
Fieldbus function module in slot 2
H
82mot396