SI 6TU - SI 18TU
2
Purpose of the Heat Pump
2.1 Application
The brine-to-water heat pump is to be used exclusively for the
heating of heating water. It can be used in new or previously ex-
isting heating systems. A mixture of water and antifreeze (brine)
is used as the heat transfer medium in the heat source system.
Borehole heat exchangers, ground heat collectors or similar
systems can be used as the heat source system.
The circulating pump(s) must be controlled using the heat
pump manager.
If function-relevant or safety-relevant pump functions, such as
integration of the heat pump into the building management
system, are not supported, then this can result in loss of war-
ranty and cause a write-off of the heat pump.
The circulating pump(s) and the heat pump controller must al-
ways be ready for operation.
The specifications in the technical documents must be fol-
lowed, particularly limit values for the minimum and – if availa-
ble – maximum warm/cold water volume flow.
2.2 Operating Principle
The heat generated by the sun, wind and rain is stored in the
ground. This heat stored in the ground is collected at a low tem-
perature by the brine circulating in the ground collector, ground
coil or similar device. A circulating pump then conveys the
"heated" brine to the evaporator of the heat pump. There the
heat is given off to the refrigerant in the refrigerating cycle. This
cools the brine so that it can once again absorb thermal energy
in the brine circuit.
The refrigerant is drawn in by the electrically driven compres-
sor, compressed and "pumped" to a higher temperature level.
The electrical power needed to run the compressor is not lost in
this process. Most of it is absorbed by the refrigerant.
Subsequently, the refrigerant is passed through the condenser
where it transfers its heat energy to the heating water. Depend-
ing on the set operating point (thermostat setting), the heating
water is thus heated up to a max. of 62 °C.
www.dimplex.eu
3
Basic Device
The basic device consists of a heat pump for indoor installation
wired ready for use with metal casing, switch box and inte-
grated heat pump manager. The refrigeration circuit is "hermet-
ically sealed" and contains the fluorinated refrigerant R410A in-
cluded in the Kyoto protocol. Information on the GWP value
and CO
equivalent of the refrigerant can be found in the chap-
2
ter Device information. The refrigerant is CFC-free, non-ozone
depleting and non-combustible.
All components required for the operation of the heat pump are
located on the control panel. An external temperature sensor
including fixing accessories and a dirt trap are supplied with the
heat pump. The supply for the load current and the control volt-
age must be installed by the customer.
The supply lead of the brine circulating pump (to be provided
by the customer) must be connected to the control panel. If re-
quired, a motor protection device and/or contactor must be
provided here.
The customer must provide both the heat source system and
the brine circuit manifold.
1)
Liquifier
2)
Control panel
3)
Evaporator
4)
Compressor
5)
Filter dryer
6)
Economizer
7)
Expansion valve
452235.66.22b · FD 0507
English
EN-3