Heaty Racun 300 Advanced Plus | Dismantling and disposal
7.2 Removal
To disassemble the device, proceed as follows:
1 Turn off the device and disconnect the power supply from the mains,
as described in section "5.4 Switching off the device" on page 46.
2 Discharge energy storage devices such as springs or capacitors when
available.
3 Make sure that any residual pressure has been released.
To do this, open the drain taps.
4 Disconnect the appliance's pipes from the heating or cooling system.
5 Empty the remaining amounts into a drain.
6 If you want to store the device or take it out of service, empty
the device completely.
7 If you want to dispose of the device, disassemble the device using
suitable tools in its assemblies.
7.3 Disposal
Dispose of components and operating materials properly and in an environmentally
friendly manner.
Please observe the legal and company regulations.
54
Technical data | Heaty Racun 300 Advanced Plus
8
Technical data
In this section you will find technical data about the device in general as well as
about the applications and components used.
8.1 General data
Heaty Racun 300 Advanced Plus
Article number
Max. filling capacity*
Max. operating pressure
Ø Circulation capacity in the bypass for magnetite separation
& filtration
Ø Circulation capacity in the bypass during treatment and
filtration
Capacity at 420 μS/cm to < 100 μS/cm**
Power supply
Weight (including mixed bed resin filling)
Contents Vadion pH-Control
Suitable for hot water up to 80 °C
Bypass capable
100481-SL
3,000 l/h
6 bar
Adjustable from 1,800 to
7,200 l/h
approx. 2,400 l/h
9.360 l
230 V / 50/60 Hz
approx. 143 kg
63 l
55