To regulate the flow rate, proceed as follows:
1.
Use the display (1) to draft
flow rate to which the valve is
should be provided.
2.
Use the ring (2) to slide open,
which under normal condi-
tions conditions the flow of
the
medium through the
passage flow meter (3)
prevented.
3.
Keep the slider open and
make the setting on the valve
control spindle (4) with a 9 mm
spanner for sizes from 1/2" to
1 1/4" or with a 12 mm spanner
for sizes from 1 1/2" to 2". The
set flow rate is indicated by the
metal ball (5) in a transparent
guide (6), next to which there is
a scale on which the value can
be read in litres per minute.
4.
After adjustment, release the ring
(2) of the flow meter slide; a built-in
spring b causes it to automatically
return to the closed position.
5.
The display (1) can be used to note
the setting made for later checks.
24
3
1
2
4
5
6
1
2
Device description | Heaty Racun 300 Advanced Plus
Safety instructions
If the adjustable volumetric flow meters with built-in flow meter are not correctly
installed, commissioned and maintained as described in this manual, they may not
function correctly and may pose a danger to the user.
Clean the pipes of any deposits, rust, incrustations, welding residues and other
contaminants.
As with any hydraulic circuit, special attention must be paid to cleaning the entire
system. Check the tightness of all connection fittings. For optimal operation, the air
contained in the medium must be released.
For safety reasons, leak tests using compressed air on the entire system and es-
pecially on the valves are not recommended due to the high compressibility of air.
When designing the hydraulic connections, make sure that the thread of the valve
body is not mechanically overstressed.
Over time, damage may occur, resulting in leaks and property damage and/or per-
sonal injury.
Water temperatures above 50°C can cause severe scalding. During installation,
commissioning and maintenance of the valve, the necessary precautions must be
taken to ensure that these temperatures do not endanger persons.
Any use other than that intended is prohibited.

3.12 Output filter cartridge

The output filter cartridge serves to protect against damage to the suction lance
and head nozzle in the cartridge to avoid resin leakage.
3.13 Solenoid valve
The solenoid valve is closed when de-energized and switches off the drinking water
supply during pressure-controlled make-up if the set limit for the maximum make-
up is exceeded.
3.14 Filling/refilling connection
The drinking water pipe is connected to the filling/refill connection in order to fill a
heating or cooling system.