Commissioning
Point
Sensor signal
X value
(mA)
4.0
Display value
Y value
3
(m
)
0
!
Function (menu item)
Point
X value
Y value
96
– Numeric display should show 1500 (m
– Bar graph should show 100%
– 20 mA should be present at the analog output
Point
Point
1
2
3
X value
X value
4.32
4.64
Y value
Y value
20
50
The following parameters must be configured for the example above:
Menu
LIN. TABLE / M 21
LINPOINTS 1 to 10 / M23 to 32
ANALOG OUT / M 3
DISPLAY / M 2
Note!
®
ReadWin
2000 operating software supports the generation of a tank linearization table.
Here you can find a tank linearization generator which you can use to generate the linearization
table for standard and customer-specific tanks.
6.3.10
Support points of linearization table - LINPOINTS 1..X/
M23..MXX
Displays the set value pairs of the linearization table. This menu item is only visible if a linearization
table was configured under Section 6.3.9 and "Yes" was selected in the "Show points" parameter in
the "LIN. TABLE/M21" menu.
Parameter setting
Used
Discard
-99999..99999
-99999..99999
3
)
Point
Point
Point
4
5
6
X value
X value
X value
4.96
5.28
5.6
Y value
Y value
Y value
85
115
160
Function (menu item)
Counts
Dimension
Show points
Each point
Each X value
Each Y value
Ref. num
Out range
Fail mode
Fail value
Ref. num.
Ref. bargraf
Use or discard support point.
X-value of the linearization table. Corresponds to the input value.
Y-value that belongs to the previous X-value. Corresponds to the converted mea-
sured value.
Point
Point
Point
7
8
9
X value
X value
X value
5.92
6.24
6.56
Y value
Y value
Y value
210
280
400
Setting value
Number of support points (10)
Dimension of lin. value (m
Display support points (Yes)
Use point (Used)
X-value (as in table above)
Y-value (as in table above)
Output value (lin tab)
Signal type (0-20 mA)
Failsafe mode (const)
Value in event of error (21 mA)
Reading on display (lin. table)
Signal source for bar graph (lin tab)
Description
Endress+Hauser
RIA452
Point
10
X value
20.0
Y value
1500
3
)