RIA452
Endress+Hauser
3
Installation
3. 1
Installation conditions
The permitted ambient conditions (see Section 10 "Technical data") must be observed when install-
ing and operating. The device must be protected against the effects of heat.
3.1.1
Dimensions
Please note the installation depth of 150 mm (5.91 inches) for the measuring instrument plus cable.
Additional dimensions are provided in Fig. 3 and Section 10 "Technical data".
3.1.2
Mounting location
Installation in panel with 92x92mm cutout (as per EN 60529). The mounting location must be free
from vibrations.
3.1.3
Orientation
Horizontal +/- 45° in every direction.
3. 2
Installation instructions
The required panel cutout is 92x92 mm (3.62x3.62 inches). Please note the installation depth of
150 mm (5.91 inches) for the measuring instrument plus cable.
Fig. 3:
Installation in panel
1.
Push the device with the sealing ring (item a) through the panel cutout from the front.
2.
Keep the device horizontal and suspend the two fixing clips (item b) in the recesses provided.
3.
Tighten the screws of the fixing clips evenly with a screwdriver.
4.
Remove the protective strip from the display.
The dimensions of the process display unit are provided in the "Technical data" Section.
Installation
65