Commissioning
!
Function (menu item)
Ref. num.
Out damp
Out range
Dec. point
Out 0%
Out 100%
Offset
Fail mode
Fail value
Simu mA
Simu V
80
6.3.3
Analog output - ANALOG OUT/M3
All configurable parameters for the analog output can be found under the analog output menu item
which is marked as ANALOG OUT in the device.
Note!
This item is only available if the "Analog output" option is available in your device.
Parameter setting
Input
Lintab
0..99.9
0.0
Off
0 - 20 mA
4 - 20 mA
0 - 10 V
2 - 10 V
0 - 1 V
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
-99999..99999
0.0
-99999..99999
100.0
-999.99..999.99
0.00
Hold
const
Min
Max
0..999.99
0.00
OFF
0.0 mA
3.6 mA
4 mA
10 mA
12 mA
20 mA
21 mA
OFF
0.0 V
5.0 V
10.0 V
Description
Selects which value is output at the analog output.
• Input = measured value
• Lintab = linearized measured value
Signal damping of measuring input with 1st order low pass. Time constant can be
selected from 0 to 99.9 sec.
Signal type of output
!
Note!
"Off" switches the output signal off completely.
Number of places after the decimal point for outputting the measured value. Can
be selected for analog signal types
Start value of the output signal
End value of the output signal
Shifts the zero point of the output curve in mA or V.
Output value if a sensor or device error occurs.
• Hold = last valid value
• Const = freely selectable value
• Min = output value 3.5 mA for 4 to 20 mA, otherwise 0 V or 0 mA
• Max = output value 22.0 mA for 0/4 to 20 mA, otherwise 1.1 V or 11 V
The freely selectable value for "Fail mode = Const" can be set here.
Current output: 0 to 22 mA
Voltage output: 0 to 11 V
Simulates the current output and outputs the selected current at the output,
regardless of the input value.
Is automatically set to OFF when the Simu mA menu item is exited.
Simulates the voltage output and outputs the selected voltage at the output,
regardless of the input value.
Is automatically set to OFF when the Simu V menu item is exited.
RIA452