Endress+Hauser RIA452 Betriebsanleitung Seite 89

Vorschau ausblenden Andere Handbücher für RIA452:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

RIA452
!
Function (menu item)
Ref. integr.
Pre-counter
Integr. base
Dec. factor
Factor
Dimension
Dec. point T
Set count A
Set count B
Totalizer
Reset total
Endress+Hauser
6.3.6
INTEGRATION/M18
This function can only be selected if the pulse output option is available in the device.
Note!
If the preset counter function (Batch) is used, digital input 1 and relay 1 and 2 are permanently
assigned to this function. Configuration for these inputs/outputs is then not possible.
Parameter setting
Input
Lintab
Off
Count up
Count down
Off
sec
Min
hour
day
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
0..99999
1.0
XXXXXXXXX
XXXXX
XXXX.X
XXX.XX
XX.XXX
X.XXXX
999999
0.0
999999
0.0
9999999
No
Yes
Description
Selects which value should be integrated.
• Input = measured value
• Lintab = linearized measured value
Activation of the preset counter
Off = preset counter off
Count up = counting up from zero to the end value
Count down = counting down from the start value to zero
Time basis for integration
Decimal point position of the conversion factor
Conversion factor
Select the dimension from the list or dimension as free text (max. 9 characters
long).
Decimal point of totalizer
End value/start value for preset counter; refers permanently to relay 1.
Value for preliminary alarm; refers permanently to relay 2.
In this position, the totalizer can be displayed and edited (e.g. assigned a default
value).
!
Note!
The counter starts again at 0 if the maximum value of 9999999 is exceeded.
Reset totalizer
!
Note!
Cannot be configured via ReadWin
Commissioning
®
2000.
89