Installation and Connection

3.
Installation and Connection
3.1

Control cabinet installation

Protective system (EN 60529):
Operation temperature:
Storage temperature:
max. heat sink temperature:
Climatic category (EN 60721-3-3):
Environment (IEC 664-1):
Vibration/Jolt according to:
The flat-rear design requires cooling measures by the machine
builder. This can be in the best case no further measure at all
(e.g. at cyclic operation with down times) up to the dissipation
of the entire, indicated heat loss at rated operation.
Protect the COMBIVERT against aggressive gases
and aerosols !
3.2

EMC-conform Installation

• Always apply the shielding of motor
and control cables over a large contact
surface on both sides.
• D i s t a n c e b e t w e e n c o n t r o l a n d
power cables at least 10...20 cm
(4...8 inch).
• L a y m o t o r a n d p o w e r c a b l e
separately.
• If it cannot be avoided, cross control
and power cables in a right angle.
• Install all cables as close as possible
to the mounting plate - ideal in a metal
cable duct.
• Mount COMBIVERT well conducting
with the mounting plate. Remove the
paint beforehand.
You can find further instructions
regarding the EMC-conform wiring in
the Internet at KEB.
-10...45 °C (14...113 °F)
-25...70 °C (-13...158 °F)
90 °C (194 °F)
Pollution degree 2
German. Lloyd; EN50155
Installation position and min.
distances
IP20
3K3
START
ENTER
FUNC.
F/R
SPEED
STOP
ANTRIEBSTECHNIK
START
ENTER
FUNC.
F/R
SPEED
STOP
30 mm
1 inch
ANTRIEBSTECHNIK
11