Herunterladen Inhalt Inhalt Diese Seite drucken

Mains Connection - KEB COMBIVERT F5 Installationsanleitung

Gehäuse e
Vorschau ausblenden Andere Handbücher für COMBIVERT F5:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation and Connection
3.3.3

Mains connection

Mains connection 230 V 1-phase
1 x 180...260 V AC
Protection
• Fuse (see chapter 2.3) or
• power protective switch
• 1-phase inverter RCD type A or type B
• 3-phase inverter RCMA with separator or
RCD type B
• at DC-supply pay attention to the
permissible voltage range of the fuses
DC-connection 230 V-class
250...370 V DC
���
PE
PE
L1
L1
N
N/L2
W
L3
++
--
PB
U
V
W
T1
T2
���
PE
L1
N/L2
L3
+
++
-
--
PB
U
V
W
T1
T2
Mains connection 230 V 3-phase
3 x 180...260 V AC
Mains connection 400 V 3-phase
3 x 305...500 V AC
DC-connection 400 V-class
420...720 V DC
���
PE
PE
L1
L1
L2
N/L2
L3
L3
++
--
PB
U
V
W
T1
T2
���
PE
PE
L1
L1
L2
L2
L3
L3
++
--
PB
U
V
W
T1
T2
���
PE
L1
L2
L3
+
++
-
--
PB
U
V
W
T1
T2
13

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis