14) Only use approved and appropriately identified ex-
tension cables for use outdoors (H07RN).
15) If extension leads or mobile distribution networks
are used, the resistance value must not exceed
1.5 Ω. As a guideline value, the total length of lines
for a cross-section of 1.5 mm² should not exceed
60 m, and for a cross-section of 2.5 mm², 100 m
should not be exceeded.
16) Never operate the power generator during rain or
snowfall.
17) Always switch off the engine during transport and
refuelling.
18) Fuel is combustible and highly flammable. Do fuel
the unit during operation. Do not fuel the unit when
someone is smoking or near open flames. Do not
spill any fuel.
19) Do not refuel or empty the tank near open light, fire
or flying sparks. Smoking prohibited!
20) Give the power generator a secure, level place.
Turning and tilting or changing location during op-
eration are forbidden.
21) Place the power generator at least 1 m away from
walls or connected devices.
22) Children must be protected by ensuring that they
stay a safe distance away from the inverter power
generator.
23) Some parts of the reciprocating internal com-
bustion motor are hot and may cause burns. The
warnings on the generator must be observed.
24) Values specified in the technical data under sound
power level (L
) and sound pressure level (L
WA
represent emission levels and are not necessari-
ly safe working levels. Since there is a correlation
between emission and exposure levels, it cannot
be reliably used to determine any additional pre-
cautionary measures that may be required. Fac-
tors influencing the current exposure level of the
worker include the characteristics of the work-
space, other noise sources, airborne noise, etc.,
such as the number of machines and other adja-
cent processes and the length of time an operator
is exposed to the noise. The permitted exposure
level may also vary from country to country. Nev-
ertheless, this information will enable the opera-
tor of the machine to make a better assessment
of the risks and hazards. If necessary, acoustical
measurements should be taken after installation to
determine the sound pressure level.
25) Warning! Comply with the electrical safety regu-
lations applicable to the place where the inverter
power generators are used.
22 | GB
26) Warning! Consider the requirements and precau-
tionary measures in case of re-supply of a system
by inverter power generators depending on the
protective measures of this system and the appli-
cable directives.
27) Inverter power generators should only be used up
to their rated power under the rated ambient con-
ditions. If the inverter power generator is used in
conditions that do not comply with the reference
conditions according to ISO 8528-8:2016, 7.1,
and if the cooling of the engine or generator is im-
paired, e.g. as a result of operation in restricted
areas, a reduction in power is required.
28) Due to high mechanical loads, only durable rubber
hose lines (according to IEC 60245-4) or equiva-
lent equipment should be used.
29) Observe the electrical safety regulations applica-
ble to the place where the inverter power genera-
tor is used.
30) Consider the requirements and precautionary
measures in case of re-supply of a system by in-
verter power generators depending on the protec-
tive measures of this system and the applicable
directives.
Electrical safety
1.
Prior to use, the generator and its electrical equip-
ment (including lines and plug connectors) should
be checked to ensure that there are no defects.
2.
The power generating unit must not be connected
)
to another power source such as the power sup-
pA
ply of energy supply companies. In special cases
where a reserve connection to existing electrical
systems is provided, this must only be carried out
by a qualified electrician who will take into account
the differences between the operated equipment
using the public mains and operation of the power
generating unit. According to this part of ISO 8528,
the differences in the operating manual must be
specified.
3.
Protection against electric shocks depends on
the circuit breakers which are matched precisely
to the power generating unit. If a circuit breaker
must be replaced, this should be done using a cir-
cuit breaker with the same rating and performance
characteristics.