TEST SHEET
STATION:
Generator Protection Type REG316*4
Checklist
Kind of check
Relay number
Visual check for transport damage
Visual check of external wiring
Check of relay grounding
Check of supply voltage (DC/AC)
Check of settings
Check of C.T. circuits
Check of P.T. circuits
Secondary injection with test set type ......
Check of input signals
Check of signalisation/alarms
Point to point test to the SCS
Check of starting breaker failure protection
Check of tripping
Primary tests
Final check
Checked by
Date:
Signature:
UNIT:
refer to the SCS test sheets
Client
Date:
Remarks
Signature:
04-11