Herunterladen Inhalt Inhalt Diese Seite drucken

Transport And Interim Storage; Transport; Interim Storage; Description - Ksb Upa Control Betriebsanleitung

Schaltschrank für trockenlaufschutz
Vorschau ausblenden Andere Handbücher für UPA CONTROL:
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

3

Transport and interim storage

3.1

Transport

Transport of the equipment requires proper preparation and
handling. Prior to dispatch, the equipment was tested and in-
spected to ensure full compliance with specifications. Conse-
quently, the equipment should be in perfect electrical and
mechanical condition upon arrival at its destination. It is recom-
mended that the equipment be inspected for in-transit damage
immediately upon receipt. In case of any objections, the re-
cipient and carrier must jointly draw up a damage report.
3.2

Interim storage

The equipment shall only be stored under dry and vibration-free
conditions in its original packaging. The ambient temperature
must not be beyond the range of --10 °C to +50 °C.
4

Description

4.1

Type of current / voltage:

Single-phase a.c.
230 V 50/60 Hz
Three-phase current
400 V 50/60 Hz
Current rating:
in steps up to 25 A
(depending on equipment size)
4.2

Fields of application

Control of submersible borehole or dry-installed pumps, for
clean water only.
4.2.1

Dry running protection

The UPA Control protects your pump set if there is a lack of
water (in "Draining" mode only). A red indicator lamp indicates
lack of water.
4.2.2
Water level control
Monitoring the water level of deep wells, tanks, etc.
4.3
Indicator lamps
Yellow:
Availability
Red
Lack of water
Flashing red light:
Cut-in delay
4.4
Scope of supply
Included in the scope of supply are:
Electrodes
4 cable glands (supplied, but not fitted)
1 spare fuse
On request: 1 thermal relay (supplied, but not fitted)
Make: Télémécanique or ABB.
14
All manuals and user guides at all-guides.com
5
-- Connection to the power supply must be effected by a
-- The electrical installation must be carried out in accordance
-- An earth leakage circuit breaker (sensitivity 30 mA) must be
-- Make sure that the electrical connections are not exposed to
-- UPA Control must not be operated in a swimming pool or
-- Disconnect the control unit from the mains prior to carrying
-- Protection against over-voltage (lightning protection):
6
Four holes in each corner of the housing rear panel are pro-
vided to accommodate the fastening screws.
6.1
Caution
-- The thermal relay must be set to match the current rating of
-- For mounting the thermal relay, insert the 3 plugs under ter-
-- Connect the free wires 95 and 96 to the corresponding ther-
-- The current rating to be set on the thermal relay is calculated
-- Set the indicator in the top part of the relay to the calculated
-- Connect the control unit in accordance with the available
Ensure that the fuse is in the correct holder:
-- "400 V" holder for a supply voltage of 380--400 V
-- "230 V" holder for a supply voltage of 220--230 V
6.2
-- The max. cable length per electrode is 330 m.
-- For mounting and connecting the electrodes to the cable

Safety regulations

trained electrician only.
with the VDE 0100/0113 standards and/or with the relevant
regulations applicable in the country of use. It is imperative to
provide for appropriate earthing.
installed in the power supply line (directly in front of the UPA
CONTROL).
humidity.
pond, not even if there isn't any person in the water.
out any work on it.
High voltages may temporarily occur during thunderstorms.
They may cause permanent damage to the motor windings
and the pump set's insulation.
Consult your electrician for suitable lightning protection
measures.
Installation
Connection to power supply
(see wiring diagrams)
the pump set.
minals 2T1, 4T2, 6T3 of the contactor and tighten the ter-
minal screws.
mal relay terminals.
as follows:
0.9 x I
(I
= rated current of pump set in A).
N
N
value.
mains supply (single- or three-phase current). In case of
single-phase operation, bridge terminal 4T2 of the thermal
relay and terminal L3 of the power supply terminal strip.
Connecting the electrodes
A one-wire cable 1 x 1.5 mm
used or GROGNT (drinking water).
please observe the mounting instructions No. 4 0 8066 290 4
supplied with the set of electrodes.
UPA CONTROL
2
, type U1000 R02V must be