5. Commissioning, operation
5.4.1 Pin assignment of analogue output
Abbreviations, definitions
Signal
Description
UB
Voltage source for sensor
UB+
Sensor-supply voltage (+)
UB-
Sensor-supply voltage (-)
S+
Output signal (+)
Output signal (-)
S-
0V
0V-Potential
For models F5301, F53C1 with UL, F5308 and F53C8 with UL
Output 4 ... 20 mA, 2-wire
Connector M12 x 1, 5-pin
UB+/S+
+
UB
-
UB-
A
0V/S-
Output 4 ... 20 mA, 3-wire
Connector M12 x 1, 5-pin
UB+
S+
+
UB
-
A
Output 0...10 V, 3-wire
Connector M12 x 1, 5-pin
UB+
S+
+
UB
-
V
Cable colours only apply when using the WIKA standard cable, e.g. order no.: 14259454
Operating instructions, models F5301, F53C1, F5308, F53C8, F53S8
4
3
5
1
2
4
3
5
1
2
0V/S-
4
3
5
1
2
0V/S-
Signal
Description
Ammeter
A
Voltmeter
V
+
Voltage source
-
Switch
Shield [grounding]
Signal
4 ... 20 mA, 2-wire
UB+/S+
1
3
0V/S-
Shield
Case / connector
Signal
4 ... 20 mA, 3-wire
UB+
1
S+
4
3
0V/S-
Shield
Case / connector
Signal
0 ... 10 V, 3-wire
UB+
1
S+
4
0V/S-
3
Shield
Case / connector
EN
Cable
colour
Brown
Black
-
Cable
colour
Brown
Black
Blue
-
Cable
colour
Brown
Black
Blue
-
17