Important:
Note 1: when a Local Action is Active, in order to be Active again it must first become
Normal.
Note 2: Overflow and Underflow are tested each time at least one Station is ON,
regardless of MV, if enabled.
Note 3: During Delay between Stations, if no other program is running at the same
time, all Stations are OFF and Overflow and Underflow are not tested. Overflow and
Underflow are tested again when the next programmed Station is started.
Note 4: for START, STOP, SKIP Actions the action itself takes place ONLY at time the
Sensor status or the Meter Function from Normal becomes Active.
Note 5: the START action will take place only if the selected Program(s) are Off at
time the action is applied.
Note 6: the STOP and SKIP action will take place only if the selected Program(s) are
On at time the action is applied.
Note 7: if a Delay between station is set, the SKIP action will stop the current station
and start the delay or it will stop the delay and start the next programmed station.
Note 8: for HOLD and RAIN Actions, the action starts at time the Sensor status from
Normal becomes Active and it is maintained until the status becomes Normal again
at which time Tempus Pro automatically removes the HOLD and RAIN conditions for
all selected Program(s).
Note 9: the HOLD and RAIN actions will be applied to the selected Program(s)
regardless of the Program On or Off status.
Remote Notification (available only with WiFi option installed and connected to
Internet).
When WiFi option is installed and connected to Internet, each time a Sensor or a
Meter function changes status from Normal to Active or from Active to Normal a
Notification is sent to the APP.
Setting the Sensor functions
Setting Sensor Type.
• Press the
button to access the Controller's Settings.
• Press the
or
buttons to select SENSOR.
• Press the
or
button to disable sensor or to select sensor type:
OFF sensor is disabled
nC → sensor is a Normally Closed type:
Sensor Switch Closed → then Sensor is in the Normal Status
Sensor Switch Open → then Sensor is in the Active Status
nO → sensor is a Normally Open type. Sensor becomes Active when
sensor input is Closed.
Sensor Switch Open → then Sensor is in the Normal Status
Sensor Switch Closed → then Sensor is in the Active Status.
Note: selecting OFF the following 3 settings are not visualized.
Setting Sensor Delay to Sensor Active.
• Press the
button to access the Controller's Settings.
• Press the
or
buttons to select SENS-DELAY.
• Press the
or
button to disable sensor delay or to set a delay time:
Off 1s . . . . 8m, increment in seconds
In order for the Sensor input to be considered Normal or Active following any sensor
status change (open to close or close to open) the new status must be maintained
longer than the time set for Sensor Delay, plus 1 second.
Note: SENS-DELAY page is available only if SENSOR is not set to OFF.