Connect the cables
Connect the cables in the junction box in accordance with
the electrical system at the location. See the illustration
below. The terminal blocks must be tightened to a torque
of 5 Nm.
If you install the system on a three-phase IT network,
we recommend that four-core cable be used in case
Electrical connection
There are four possible connection variants, depending on whether three-phase
or single-phase is used, and whether a TN network, TT network or IT network is
used, as shown under or on the label on the back plate.
L1
L2
L3
N
PE
L1
L1
L2
L3
N
PE
L1
L2
L1
L2
L3
N
PE
L1
L2
TN 3-fase
TN 1-fase
TN three-phase
TN single-phase
6
Test the connections
Test the connections in accordance with
your chosen configuration.
12
N
PE
L1
L2
L3
PE
L3
N
PE
L1
L2
L3
N
PE
L3
N
PE
L1
L2
L3
N
PE
IT 3-fase
IT three-phase
23 0 V
a transformer is installed in order to provide better
protection in the future. This will mean that the neutral
connection can be made in the fuse box rather than on
each individual charging point, which will make it easier to
carry out future upgrades.
L1
L3
PE
L1
L2
L3
N
PE
L1
L2
L3
N
PE
IT 1-fase
IT single-phase
You must not mix up the phases on the charging
stations in the installation. If the phases do
become mixed up, the phase balancing will
not work and the fuses may trip.
23 0 V