Herunterladen Inhalt Inhalt Diese Seite drucken

Diagnosis Suppression - Balluff Bos R254K-Uui-Re10-S4 Konfiguration

Io-link-konfiguration
Vorschau ausblenden Andere Handbücher für BOS R254K-UUI-RE10-S4:
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

BOS R254K-UUI-RE10-S4
Photoelectric Sensors
6
System Functions (continued)
6.2

Diagnosis Suppression

6.2.1
Description
Diagnosis suppression is used to suppress diagnosis
messages from the device. There are two possibilities here:
Diagnosis suppression level that permits a general
suppression of messages of a certain level (message,
warning, error).
Event-code suppression of up to 5 events as a list or
via teach-in.
6.2.2
ISDU
Name
Index
Diagnosis
0x0070 (112)
Level
Configuration
Event Code
0x0071 (113)
Suppression
Event Code
0x0072 (114)
Suppression
Teach-In
Event Code
0x0073 (115)
Suppression
Delete
Tab. 6-4:
Diagnosis suppression – ISDU
6.2.3
Diagnosis Level Configuration
This parameter offers the possibility to select an output
level for events.
This index is part of the data management and is stored in
non-volatile memory.
Value
Diagnosis Level
0
All events
1
Warnings and errors
2
Error
3
No events
Tab. 6-5:
Diagnosis suppression – Diagnosis level configuration
www.balluff.com
Sub index
Access
0
R/W
0
R/W
1-5
R/W
0
W
0
W
Descriptions
All diagnosis messages are reported (default setting).
All warnings and errors are reported – messages are
suppressed.
Only events of type error are reported.
All diagnosis messages from the device are suppressed.
Length
Data Type
1 Byte
ENUM
10 Byte
UINT16
2 Byte
2 Byte
UINT16
2 Byte
UINT16
Data
Default
Storage
Yes
0
Yes
0
n/a
n/a
n/a
n/a
english
85