Table I – Maximum refrigerant charge allowed in a room
Maximum refrigerant charge in a room
A
room
(m
)
2
H =
H =
H =
1.15m
1.20m
1.30m
1
0.265 0.276 0.299 0.322 0.345 0.368
2
0.530 0.553 0.599 0.645 0.691 0.737
3
0.794 0.829 0.898 0.967 1.036 1.105
4
1.059 1.105 1.197 1.289 1.382 1.474
5
1.324 1.382 1.497 1.612 1.727 1.842
6
1.589 1.658 1.796 1.934 2.072 2.210
7
1.738 1.814 1.965 2.116 2.267 2.418
8
1.858 1.939 2.101 2.262 2.424 2.585
9
1.971 2.057 2.228 2.399 2.571 2.742
10
2.078 2.168 2.349 2.529 2.710 2.891
11
2.179 2.274 2.463 2.653 2.842 3.032
12
2.276 2.375 2.573 2.771 2.969 3.166
For intermediate H values, the value that corresponds to the lower
H value from the table considered.
Example:
For H = 1.25 m, the value that corresponds to " H = 1.20 m" is
considered.
For intermediate A
values, the value that corresponds to the
room
lower A
value from the table is considered.
room
Example:
For A
= 10.5 m
2
, the value that corresponds to
room
" A
= 10 m
2
" is considered.
room
Table II – Minimum floor area
m
c
(kg)
H =
H =
H =
1.15m
1.20m
1.30m
1.84
7.84
7.20
6.15
1.86
8.02
7.36
6.27
1.88
8.19
7.52
6.41
1.90
8.36
7.68
6.54
1.92
8.54
7.84
6.68
1.94
8.72
8.01
6.82
1.96
8.90
8.17
6.96
1.98
9.08
8.34
7.11
2.00
9.27
8.51
7.25
2.02
9.45
8.68
7.40
2.04
9.64
8.85
7.54
2.06
9.83
9.03
7.69
2.08 10.02
9.21
7.84
2.10 10.22
9.38
8.00
2.12 10.41
9.56
8.15
4
( m
) (kg)
max
H =
H =
H =
H =
1.40m
1.50m
1.60m
1.70m
0.391
0.783
1.174
1.566
1.957
2.349
2.570
2.747
2.914
3.071
3.221
3.364
Minimum floor area
( A
(m
))
2
min total
H =
H =
H =
H =
1.40m
1.50m
1.60m
1.70m
5.71
5.33
4.99
4.70
5.77
5.39
5.05
4.75
5.83
5.44
5.10
4.80
5.89
5.50
5.16
4.85
5.96
5.56
5.21
4.91
6.02
5.62
5.27
4.96
6.08
5.68
5.32
5.01
6.14
5.73
5.37
5.06
6.25
5.79
5.43
5.11
6.38
5.85
5.48
5.16
6.51
5.91
5.54
5.21
6.63
5.96
5.59
5.26
6.76
6.02
5.65
5.31
6.89
6.08
5.70
5.37
7.03
6.14
5.75
5.42
m
c
(kg)
H =
H =
1.15m
1.20m
2.14 10.61
9.74
H =
1.80m
2.16 10.81
9.93
0.414
2.18 11.01 10.11
0.829
2.20 11.21 10.30
1.243
2.22 11.42 10.49
1.658
2.24 11.62 10.68
2.072
2.26 11.83 10.87
2.487
2.27 11.94 10.96
2.721
For intermediate H values, the value that corresponds to the lower
H value from the table considered.
2.909
Example:
For H = 1.25 m, the value that corresponds to " H = 1.20 m" is considered.
3.085
For intermediate m
m
value from the table is considered.
3.252
c
Example:
3.411
If m
= 1.85 kg, the value that corresponds to " m
c
considered.
3.562
Systems with total refrigerant charge lower than 1.84 kg are not
subjected to any room area requirements.
Charges above 2.27 kg are not allowed in the unit.
Table III – Minimum venting opening area for natural ventilation
m
excess
m
m
(kg) =
c
max
(kg)
(kg)
m
-
c
m
max
2.27
0.1
2.17
2.27
0.3
1.97
2.27
0.5
1.77
H =
2.27
0.7
1.57
1.80m
2.27
0.9
1.37
4.44
2.27
1.1
1.17
4.49
2.27
1.3
0.97
4.54
2.27
1.5
0.77
4.58
2.27
1.7
0.57
4.63
2.27
1.9
0.37
4.68
For intermediate H values, the value that corresponds to the lower
H value from the table considered.
4.73
Example:
4.78
For H = 1.25 m, the value that corresponds to " H = 1.20 m" is
considered.
4.83
For intermediate m
higher m
value from the table is considered.
excess
4.87
Example:
m
= 1.45 kg, the value that corresponds to " m
4.92
excess
is considered.
4.97
5.02
5.07
5.12
Minimum floor area
( A
(m
))
2
min total
H =
H =
H =
H =
1.30m
1.40m
1.50m
1.60m
8.30
7.16
6.24
5.81
8.46
7.29
6.35
5.86
8.62
7.43
6.47
5.92
8.77
7.57
6.59
5.97
8.94
7.70
6.71
6.03
9.10
7.84
6.83
6.08
9.26
7.98
6.96
6.13
9.34
8.06
7.02
6.17
values, the value that corresponds to the higher
c
Minimum venting opening area
( VA
) (cm
)
2
min
H =
H =
H =
H =
H =
1.15m
1.20m
1.30m
1.40m
1.50m
634
621
596
575
555
576
564
541
522
504
517
506
486
469
453
459
449
431
416
402
400
392
377
363
351
342
335
322
310
299
283
277
267
257
248
225
220
212
204
197
170
163
157
151
146
117
112
103
98
95
values, the value that corresponds to the
excess
H =
H =
1.70m
1.80m
5.47
5.16
5.52
5.21
5.57
5.26
5.62
5.31
5.67
5.36
5.72
5.40
5.77
5.45
5.80
5.48
= 1.86 kg" is
c
H =
H =
H =
1.60m
1.70m
1.80m
538
522
507
488
473
460
438
425
413
389
377
367
339
329
320
290
281
273
240
233
227
191
185
180
141
137
133
92
89
86
= 1.6 kg"