3.20 Load Control Menus

The Load Control menu displays the status of the Load
Control Module (LCM) or load shed kit inputs and
outputs, and allows a test of the load control output
relays. This menu appears only if an LCM, load shed kit,
or Model RXT transfer switch with the combined
interface/load management board is connected.
Load
---->
Control
Figure 3-25 Load Control Module (LCM) Status Menu
TP-6804 1/15
Generator
Current:
123 %
Load
---->
Control 1
<---- Return
Generator current is displayed as a percent of the
maximum generator capacity. The load control module
adds and sheds loads based on the generator current.
The test function cycles the relays in the order of their
priority.
For detailed information about the LCM
operation, refer to TT-1574, provided with the LCM kit.
For the load shed kit, see TT-1609.
Test Outputs
Push Select (blinking)
Input 1:
In/Active
Input 2:
In/Active
Output 1:
Add/Shed
Output 2:
Add/Shed
Output 3:
Add/Shed
Output 4:
Add/Shed
Output 5:
Add/Shed
Output 6:
Add/Shed
<---- Return
Section 3 RDC2 Controller Operation