Praesideo 4.0
Clause/Requirement
EN 54-16:2008 (E)
(this text is used for
certification )
b.
a description of which
areas of memory are
used for the various pur-
poses (e.g. the program,
site specific data and
running data);
c
a description of how the
software interacts with
the hardware of the
VACIE.
Where dynamic memory
management is
employed, a separation
shall be implemented
between the program,
site specific data and
running data and this
shall be described in
connection with the
method of memory allo-
cation.
14.2.2
The manufacturer shall
prepare and maintain
detailed design docu-
mentation. This need not
be submitted to the test-
ing authority but shall be
available for inspection in
a manner which respects
the manufacturer's rights
of confidentiality. This
documentation shall
comprise at least the fol-
lowing:
Bosch Security Systems B.V.
Paragraf/Anforderung
Compliance
EN 54-16:2008 (D)
(dieser Text dient nur
(this text is used for
zur Information)
certification )
eine Beschreibung,
Memory usage is described in
welche Speicherbe-
the system architecture
reiche für welche ver-
document.
schiedenen Zwecke
benutzt werden (z. B.
Programm, anlagen-
spezifische Daten,
Betriebsdaten);
eine Beschreibung,
Hardware software interaction
wie die Software auf
is described in a set of
die Hardware der SAZ
Hardware-Software Interface
einwirkt.
documentation.
Wird ein dynamisches
The program is located in
Speichermanagement
separate Flash EPROMs that
verwendet, muss eine
are reserved for the program
Trennung zwischen
executable.
Programm, anlagen-
spezifischen Daten
The message data is stored on
und Betriebsdaten
a separate Flash card.
vorgenommen wer-
den und in Verbindung
The site specific configuration
mit der Art der Spe-
data is stored on the Flash file
icherzuweisung bes-
system.
chrieben werden.
The running data (static
variables, stacks and heap
data) is stored in RAM.
After loading the program
executable from Flash EPROM
into RAM, the code space and
the running data are separated
from each other: the code
space is in the bottom area of
the RAM and the running data
takes up the remainder.
Dynamic memory is allocated
from the heap using the
VxWorks (first fit policy based)
memory manager.
The file system that, apart from
storing the site specific data,
also stores the logging
information and configuration
web pages, is a Flash EPROM
based DOS FAT file system
that is managed by the
VxWorks Flash file system
manager.
Der Hersteller muss
The software design
eine detaillierte Doku-
documents contain detailed
mentation zur Aus-
design documentation.
führung der Software
Furthermore code comments
erstellen und pflegen.
also contain detailed design
Diese muss nicht zur
documentation.
Begutachtung ein-
gereicht werden, ist
jedoch zur Einsicht in
einer Weise bereitzu-
halten, welche die
Rechte des Herstell-
ers auf Vertraulichkeit
wahrt. Diese Doku-
mentation muss mind-
estens Folgendes
enthalten:
Installations- und Bedienungsanleitung
Erfüllung
(dieser Text dient nur zur
Information)
Der Speicherbedarf wird in der
Systemarchitekturunterlage
beschrieben.
Die Interaktion von Hardware
und Software wird in der Hard-
ware-Software-Schnittstellen-
dokumentation beschrieben.
Das Programm befindet sich in
separaten Flash EPROMs, die
für das ausführbare Programm
reserviert sind.
Die Meldungsdaten werden
auf einer separaten Flash-Karte
gespeichert.
Die programmspezifischen
Konfigurationsdaten werden
auf dem Flash-Dateisystem
gespeichert.
Die laufenden Daten (statis-
tische Variablen, Stapel und
Haldendaten) werden im RAM
gespeichert.
Nach dem Laden des vom
Flash EPROM in den RAM
auszuführenden Programms,
werden die Codekapazität und
die laufenden von einander
getrennt: Die Codekapazität
befindet sich im unteren
Bereich des RAM und die
laufenden Daten im restlichen
Bereich. Der dynamische
Speicher wird von der Halde
über den Speichermanager
VxWorks (First-Fit richtlinien-
basiert) zugewiesen.
Das Dateisystem, das neben
dem Speichern programm-
spezifischer Daten auch die
Anmeldeinformationen und
Konfigurations-Webseiten
speichert, ist ein auf Flash
EPROM basiertes DOS FAT
Dateisystem, das über den
VxWorks Flash-Dateisystem-
manager verwaltet wird.
In den Programmierungsdoku-
menten ist eine detaillierte
Konstruktionsdokumentation
enthalten. Außerdem ist auch
in den Codekommentaren eine
detaillierte Konstruktionsdoku-
mentation enthalten.