Praesideo 4.0
Clause/Requirement
EN 54-16:2008 (E)
(this text is used for
certification )
a
a visible indication by
means of a separate light
emitting indicator (the
general fault warning
indicator);
b
a visible indication for
each recognised fault as
specified in 8.2.3, 8.2.4,
8.3 (if provided), 8.4 (if
provided) and 8.5 and
c
an audible indication, as
specified in 8.6.
8.2.2
If the indication is on an
alphanumeric display,
which cannot simulta-
neously indicate all of the
faults because of its lim-
ited capacity, at least the
following shall apply:
a
the presence of fault indi-
cations which have been
suppressed shall be indi-
cated;
b
suppressed fault indica-
tions shall be capable of
being displayed by
means of a manual oper-
ation at access level 1 or
2 which interrogates only
fault indications.
Bosch Security Systems B.V.
Paragraf/Anforderung
Compliance
EN 54-16:2008 (D)
(dieser Text dient nur
(this text is used for
zur Information)
certification )
eine optische Anzeige
The Praesideo system provides
mittels eines sepa-
a visible indication when it is in
raten lichtemittier-
the fault warning condition via
enden
the fault LED of the call
Anzeigeelements
stations, output contacts, key
(Störungssammelan-
indicators of call station keys,
zeigeelement);
the fixed fault output contact of
the network controller and the
front panel menu of the
network controller.
The installer must mount a
yellow (flash) light to indicate
the fault warning condition,
clearly visible from the front
side of the rack, behind the
glass door of the rack.
eine optische Anzeige
The Praesideo system offers
für jede erkannte
two ways of visual indication of
Störung, wie in 8.2.3,
individual faults: via the front
8.2.4, 8.3 (wenn zutr-
panel menu of the network
effend), 8.4 (wenn
controller and via the
zutreffend) und in 8.5
Praesideo logging application.
angegeben; und
eine akustische
The Praesideo system provides
Anzeige, wie in 8.6
an audible fault indication
angegeben.
when it is in the fault warning
condition via output contacts
and the fixed audible fault
output contact of the network
controller.
Erfolgt die Anzeige auf
einem alphanu-
merischen Display,
das aufgrund seiner
eingeschränkten
Anzeigekapazität nicht
alle Störungen gle-
ichzeitig anzeigen
kann, muss mindes-
tens Folgendes erfüllt
sein:
das Vorhandensein
The network controller
von unterdrückten
alphanumeric display is used
Störungsmeldean-
to indicate the fault warning
zeigen muss angezeigt
condition and all individual
werden;
faults.
The normal display information
of the network controller is
automatically overruled when
there are faults present, i.e.
when the system enters the
fault warning state. The display
of the network controller
indicates the number of faults
present.
unterdrückte Störungs-
The individual faults are
meldeanzeigen müs-
presented in the 'Faults' menu
sen durch eine
of the front panel menu of the
manuelle Bedienung in
network controller. Manual
Zugangsebene 1 oder
operation is needed to display
2, die nur Störungs-
and navigate through the
meldeanzeigen
individual faults. Each
abfragt, angezeigt
individual fault is shown in a
werden können.
submenu of the 'Faults' menu.
Installations- und Bedienungsanleitung
Erfüllung
(dieser Text dient nur zur
Information)
Das Praesideo System bietet
über die Störungs-LED der
Sprechstellen, der Ausgang-
skontakte, der Tastenan-
zeigen, der
Sprechstellentasten des festen
Störungsausgangskontakts
des Netzwerkcontrollers und
des Menüs an der Vorderseite
des Netzwerkcontrollers eine
optische Anzeige, wenn es
sich im Störungsmelde-
zustand befindet.
Der Installateur muss eine
gelbe Leuchte (Blinkleuchte)
einbauen, sodass der
Störungsmeldezustand
angezeigt wird und klar und
deutlich von der Vorderseite
des Racks hinter der Glastüre
des Racks sichtbar ist.
Das Praesideo System bietet
zwei Möglichkeiten der optis-
chen Anzeige einzelner Störun-
gen: über das Menü an der
Vorderseite des Netzwerkcon-
trollers und über die Praesideo
Einlog-Anwendung.
Das Praesideo System bietet
eine akustische Störungsan-
zeige, wenn es sich im
Störungsmeldezustand befin-
det, und zwar über Ausgang-
skontakte und den akustischen
Störungs-Ausgangskontakt
des Netzwerkcontrollers.
Das alphanumerische Display
des Netzwerkcontrollers wird
zur Anzeige des Störungsmel-
dezustands und aller anderen
Störungen verwendet.
Die normalen Display-Informa-
tionen des Netzwerkcontrollers
werden automatisch außer
Kraft gesetzt, wenn Störungen
vorhanden sind, d. h., wenn
das System in den Störungs-
meldezustand schaltet. Das
Display des Netzwerk-
controllers zeigt die Anzahl der
aktuell vorhandenen Störungen
an.
Die einzelnen Störungen wer-
den im Störungsmenü des
Menüs an der Vorderseite des
Netzwerkcontrollers angezeigt.
Es ist ein manuelles Vorgehen
erforderlich, um die einzelnen
Störungen anzuzeigen und
durch die einzelnen Störungen
zu navigieren. Jede einzelne
Störung wird in einem Unter-
menü des Störungsmenüs
angezeigt.
IUI-PRAESIDEO_4.0 | V1.0 | 2013.01
de | 55