Clause/Requirement
EN 54-16:2008 (E)
(this text is used for
certification )
13.3

Mechanical design

requirements
13.3. 1
The cabinet of the VACIE
shall be of robust con-
struction consistent with
the method of installation
recommended in the
documentation. It shall
meet at least classifica-
tion IP30 of
EN 60529:1991+
A1:2000.
13.3.2
All interconnections and
settings inside the cabi-
net shall be accessible at
level 3.
13.3.3
The VACIE may be
housed in more than one
cabinet. If the documen-
tation shows that the
cabinets may be installed
in locations distributed
within the protected pre-
mises, then all of the
mandatory manual con-
trols and indicators shall
be on one cabinet or on
cabinets declared to be
only suitable for mount-
ing adjacent to each
other.
13.3.4
All mandatory manual
controls and light emit-
ting indicators shall be
clearly labeled to indicate
their purpose. The labels
shall be legible at 0.8 m
distance in an ambient
light intensity from
100 lux to 500 lux.
Bosch Security Systems B.V.
Paragraf/Anforderung
Compliance
EN 54-16:2008 (D)
(dieser Text dient nur
(this text is used for
zur Information)
certification )
Anforderungen an die
Praesideo is compliant.
mechanische Aus-
führung
Das Gehäuse der SAZ
The Praesideo call station
muss eine mit der in
product range, network splitter
der Dokumentation
and fiber interfaces comply
empfohlenen Installa-
with this requirement. The
tionsweise überein-
installer must implement this
stimmende aus-
requirement for 19"-units, by
reichende Festigkeit
means of using a correct 19"-
aufweisen. Das
frame, meeting at least
Gehäuse muss mind-
classification IP30 of
estens der Schutzart
EN 60529:1991+A1:2000.
IP 30 nach
The EN 54-16 certification of
EN 60529:1991,
Praesideo includes the 19"-
geändert durch
rack. A rack must be used from
EN 60529:1991/
the list of approved racks.
A2:2000 entsprechen.
Alle Verbindungen und
The installer must ensure that
Einstellungen innerh-
the physical access to the
alb des Gehäuses
Praesideo system is restricted
müssen in Zugangse-
to access level 3, then
bene 3 erreichbar
accessibility to all
sein.
interconnections and settings
inside the cabinet (e.g.
interconnections between the
system elements) is restricted
to this access level.
Die SAZ darf aus
The IUI shows that the
mehreren Gehäusee-
Praesideo cabinets may be
inheiten bestehen.
installed in locations
Wenn aus der Doku-
distributed within the premises.
mentation hervorgeht,
One dedicated Praesideo call
dass die Gehäuse
station with call station
verteilt im Sicherungs-
keypad(s) or call station kit
bereich angeordnet
with call station keypad kit(s)
sein dürfen, müssen
can then be used for all of the
alle verbindlich vor-
mandatory controls and
zusehenden Bedien-
indicators. The installer shall
und Anzeigeelemente
take care of proper installation
an einem Gehäuse
in order to fulfill this
oder an Gehäusen
requirement.
sein, die für die auss-
chließlich unmittelbar
benachbarte Montage
vorgesehen sind.
Alle verbindlich vor-
The Praesideo call station
zusehenden Bedien-
keypad has a paper slot next to
und Anzeigeelemente
each of its programmable keys.
müssen ihrem Verwen-
The installer must provide
dungszweck entspre-
proper labels that fit into these
chend eindeutig gek-
paper slots and implement this
ennzeichnet sein. Die
requirement. Note that if the
Kennzeichnungen
call station keypad kit is used,
müssen in einem
the installer must provide
Abstand von 0,8 m bei
custom-made call station
einer Umgebungs-
keypads, including the labels.
beleuchtungsstärke
A regular font with with
von 100 lx bis 500 lx
characters of 3 mm height
lesbar sein.
offers sufficient readability in
case of high contrast between
text color and background.
Lower contrast color
selections will require bigger
characters.
Installations- und Bedienungsanleitung
Erfüllung
(dieser Text dient nur zur
Information)
Praesideo ist zertifiziert.
Das Praesideo Sprechstellen-
sortiment, der Netzwerk-Split-
ter und die LWL-Schnittstellen
entsprechen dieser
Anforderung. Der Installateur
muss diese neue Anforderung
für 19-Zoll-Einheiten mithilfe
eines ordnungsgemäßen 19-
Zoll-Rahmens der mindestens
der Klassifizierung IP30,
EN 60529:1991+A1:2000
entspricht, implementieren. Zur
Zertifizierung gemäß EN 54-16
von Praesideo gehört das 19-
Zoll-Rack. Es ist ein Rack aus
der Liste der für diesen Zweck
zugelassenen Racks zu ver-
wenden.
Der Installateur muss dafür sor-
gen, dass der physische
Zugriff auf das Praesideo Sys-
tem auf Zugangsebene 3
beschränkt ist, dann ist der
Zugriff auf sämtliche Zwischen-
verbindungen und Einstellun-
gen innerhalb des Gehäuses
(z. B. Zwischenverbindungen
von Systemelementen) auf
diese Zugangsebene
beschränkt.
In der wird IUI angezeigt, dass
die Praesideo Gehäuse inner-
halb der Räumlichkeiten an ver-
schiedenen Positionen
installiert werden kann. Eine
spezielle Praesideo Sprechs-
telle mit Sprechstellentasta-
tur(en) oder ein
Sprechstellenfeld mit Sprechs-
tellentastatur(en) kann dann für
alle obligatorischen Steuerung-
selemente und Anzeigen ver-
wendet werden.
Der Installateur hat für eine
ordnungsgemäße Installation
zu sorgen, um diese
Anforderung zu erfüllen.
Bei der Praesideo Sprechstel-
lentastatur sind neben sämtli-
chen programmierbaren Tasten
Papierschlitze angebracht. Der
Installateur hat für ordnungs-
gemäße Schilder zu sorgen,
die in diese Papierschlitze pas-
sen und muss diese
Anforderung implementieren.
Achten Sie darauf, dass wenn
das Sprechstellentastenfeld
verwendet wird, der Installa-
teur angepasste Sprechstel-
lentastaturen einschließlich
Schilder bereitstellen muss.
Ein regulärer Font mit Zeichen
von 3 mm Höhe der gut lesbar
ist, wenn zwischen Textfarbe
und Hintergrund einen hohen
Kontrast gibt. Die Auswahl von
Farben mit niedrigerem Kon-
trast erfordert größere
Zeichen.
IUI-PRAESIDEO_4.0 | V1.0 | 2013.01
de | 79