7. Description of program numbers
PN
Function
0
Input signal
EN
Parameters 1 ... 29 Used for standardised input signals. There must be no signal
Parameter ≥ 30
24
applied to the measuring input. The corresponding display values
can be manually assigned.
With parameter 1 ... 12, the input signal can be linearised.
→ For assigning display values see chapter 7.1.2 "Start and end
value"
Used for non-standardised input signals. The signal must be
applied to the measuring input and the corresponding display value
manually assigned.
→ For assigning display values see chapter 7.1.2 "Start and end
value"
WIKA operating instructions digital indicator, model DI35-M
Parameter
Resistance
30 = ≤ 100 Ω (4-/2-wire)
31 = ≤ 1 kΩ (4-/2-wire)
32 = ≤ 10 kΩ (4-/2-wire)
Sensor calibration
33 = 0/4 ... 20 mA
34 = DC -1 ... +10 V
35 = DC -1 ... + 5 V
36 = DC -500 ... +2,500 mV
37 = DC -500 ... +1,250 mV
38 = DC -500 ... +600 mV
39 = DC ±300 mV
40 = DC ±150 mV
41 = DC ±75 mV
42 = DC ±35 mV
43 = DC ±18 mV
44 = 0 ... 5 mA
45 = 0 ... 2 mA