5. Commissioning
Installing the digital indicator
1. As required, slide the unit characters into the window provided via the lateral channel.
2. Remove the mounting elements.
EN
3. Slide the seal over the digital indicator.
4. Slide the digital indicator into the control panel from the front.
Check the seal is properly seated.
5. Lock the mounting elements into place and tighten the clamping screws (max. 0.1 Nm).

5.3 Electrical connection

5.3.1 Notes on installation

The supply must comply with overvoltage category II.
Protect the voltage supply with a slow fuse of max. 0.5 A.
For the panel-mounting version, a suitable isolation device must be provided.
Route the signal input lines and signal output lines separately.
Route outward and return lines side-by-side.
Galvanically isolated potentials must be connected to a suitable point (e.g. earth or
plant ground).
For high-accuracy requirements and small measuring signals, the sensor wires
must be shielded and twisted. The shield should be connected at one end only to a
suitable equipotential bonding (e.g. measurement ground).
Avoid electrostatic discharges in the area of the terminals.
14
WIKA operating instructions digital indicator, model DI35-M