Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connection; Power Supply Connection - Helios AIR1 RH 1500 Montage- Und Betriebsvorschrift

Inhaltsverzeichnis

Werbung

Installation and Operating Instructions
ATTENTION
m
DANGER
+
NOTE
Central ventilation units AIR1 RH
The necessary equipment for outdoor installation includes:
– Sufficient insulation of the entire duct ventilation system
– Weather protection cover (AIR1-AAD)
– Exhaust air discharge hood (AIR1-AAHF)
– Outside air intake hood (AIR1-AAHA)
– Terminal box heater (AIR1-AAHK)
– Ensure that the unit has been installed at a suitable height to prevent snow entering into the unit or duct system
– The unit can be permanently installed outside using the transport attachment
The wind loads in the respective area of application must be taken into account!
The transport attachments secure the unit on the pallet during transportation These should be carefully removed during
installation, so that they can possibly be reused as secure attachments on site (see Fig. 21).
2 .2

Electrical connection

The unit must be fully isolated from the mains power supply before all maintenance and installation work and
opening the terminal compartment! The electrical connections must be carried out in accordance with the
relevant wiring diagram and must only be carried out by qualified electricians . The electrical connection must
be fully isolated until the final assembly!
The unit is equipped with a main switch and an isolator which is secured against unauthorized switching with a U-lock.
The relevant standards, safety regulations (e.g. DIN VDE 0100) and the technical connection conditions of the local
electricity supply companies must be observed.
The electrical connection of the unit takes place directly in the terminal box or at the main switch.
The controller AIR1-BE ECO or AIR1-BE TOUCH (not included in scope of delivery) is connected to the unit via an
accompanying cable. The controller is delivered with a 5 m long cable, but 10 m or 20 m long cables are also available.
The maximum controller cable length is 100 m.
In accordance with standard EN 61000-3-2, the units should be classified as "professional equipment". The connection
to a low voltage supply is permitted in so far as this has been agreed with the energy supply company.
The following circuit breakers are recommended by the manufacturer:
AIR1 RH
Phase
Type
Circuit breaker (A)
If an RCD is used, it must fulfil the following requirements:
Unit type
AIR1 RH 1500
AIR1 RH 2000
AIR1 RH 3000
AIR1 RH 5000
AIR1 RH 6000
AIR1 RH 8000
AIR1 RH 9500
AIR1 RH 12000
AIR1 RH 15000
Further information on the power supply connection of accessory components can be found in the installation and
operating instructions for the respective accessory component.

2 .2 .1 Power supply connection

Unit types: AIR1 RH 1500/2000/3000
1. Open the terminal box cover.
2. Check the thickness of the cable to be used for power connection.
1500
2000
3000
5000
~3
~3
~3
~3
C
C
C
C
10
16
20
10
RCD type
RCD protection (mA)
A
A
A
B
A
A
B
B
B
14
6000
8000
9500
12000
~3
~3
~3
~3
C
C
C
C
10
16
16
20
Leakage current (mA)
30
3,27
30
0,06
30
0,04
300
14,8
30
3,42
30
2,55
300
14,8
300
14,8
300
14,8
EN
Fig .21
15000
~3
C
20

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis