2 .3 .14 Sensor-controlled ventilation (Ventilation on demand - VOD)

The sensor-controlled ventilation operation is activated and adjusted using one or more optional air quality sensors.
Sensor-controlled ventil.
(VOD)
Yes →
→ Sensor type
Sensor type
AI2: VOC
Sensor type
AI3: CO2
Sensor-Type
AI4: Rel. humidity
Press the
button to select "YES" in the "Sensor-controlled operation" menu. Press the
OK
OK
press the
button to select the connected sensor types (AI2, AI3, AI4). After selecting the sensor types, press the
button to enter the sensor settings.
Sensor type
→ CO2/VOC
Humidity
Press the
button to enter the sensor settings. Press the
OK
OK
• Reduced: Activation of the ventilation stage "Reduced" due to the measured sensor value.
• Boost: Activation of the ventilation stage "Boost" due to the measured sensor value.
• Diff: Hysteresis
• Stop time: If the ventilation unit runs at the boost ventilation stage for longer than 2 hours, the sensor-controlled
ventilation will be interrupted for the set stop time. In case of a setting of 0 hours, the ventilation unit will continue to
run in sensor-controlled mode.
Reduced: 800 ppm
Boost: 1000 ppm
Diff: 160 ppm
Stop time: 2 h
In order to use this function, at least one air quality sensor must be connected. The sensor-controlled operating function
can only be activated by the VOD timer.
Up to 3 different or same types of sensors can be connected to a ventilation unit with 3 free analogue inputs. The hig-
hest ventilation requirement has priority.
If a room temperature sensor is connected to analogue input AI2 (KWL-FTF temperature 0-10 V sensor), only analogue
inputs AI3 and AI4 will be available for the air quality sensors.
In order to connect more than 3 sensors to a ventilation unit, the optional signal converter AIR1-SK with 6 analogue
inputs and one analogue output is available. Only the same types of sensor can be connected per signal converter
AIR1-SK.

2 .3 .15 Closing the commissioning assistant

Select "YES" to start the ventilation application.
Complete configuration and
start application
No
The following settings must still be adjusted for operation after completing the commissioning assistant:
Time and date (see section 4.0.2 a)
Timer (see section 4.0.2)
2 .4

Emergency operation/Fire mode

If the potential-free switch contact DI2 is closed, the unit will switch to emergency operation/fire mode.
Access to the settings: Log on as Admin.
OK
OK
OK
OK
OK
OK
OK
OK
button and the
OK
OK
OK
OK
48
OK
OK
OK
OK
OK
OK
OK
OK
button to select "YES" and
button to set the following settings:
OK
OK
EN

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis