4 . Mounting flange MF 100 (Accessories)
For use in case of confined space in ceilings, in thin walls and narrow shafts. Attach the MF 100 to the wall or
ceiling at a right-angle (any number possible one above the other). Then secure the fan to the MF 100 with the
enclosed screws (Fig. 10/11). Also suitable for assembling a pull cord switch (Accessories).
Fig .10
MF 100 attachable
12
Wall

Electrical connection

m The safety instructions in section 1 .2 must be observed!
− The electrical connection and initial commissioning must only be carried out by qualified electricians
according to the information in the attached wiring diagrams .
− All relevant standards, safety regulations (e .g . DIN VDE 0100), as well as the technical connection
conditions of energy suppliers are to be adhered to!
− An all-pole mains switch/isolator, with at least a 3 mm contact opening (VDE 0700 T1 7 .12 .2 / EN
60335-1)is mandatory!
− Network configuration, voltage and frequency must be consistent with the rating plate information .

Connection of supply line / Commissioning

− An NYM cable must be used, commercial maximum diameter 11 mm
− Puncture cable grommet with a round tool or directly with the supply cable (Fig.9, Pos ô )
− Remove cable jacket at least 100 mm in length. Strip insulation 7mm in length (Fig.12)
− Push cable carefully through cable grommet
− Run cable in conduit and connect according to wiring diagram (page 15)
− Check the waterproofing of the connection cable and tight clamping of the strands
− If with installed supply cable, the cable grommet does not enclose the plastic-sheathed cable evenly, the
grommet must be sealed additionally e.g. with silicone. Otherwise the IP protection expires
− The connection cable must be kept in such a way that no water can get in along the cable in case of water
exposure. The cable must not run over sharp edges!
− Check designated use of fan
− Compare mains voltage to rating plate data
− Check fan for solid mounting and professional electrical installation
− Check free movement of the impeller