ELECTRICAL AND CONTROL SETTINGS

Monobloc system - YUTAKI M
Power supply
Model
RASM-3VNE
RASM-4VNE
1~ 230V 50Hz
RASM-5VNE
RASM-6VNE
RASM-4NE
3N~ 400V
RASM-5NE
RASM-6NE
?
N O T E
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory "DHWT-(200/300)S-3.0H2E".

7.2.2 Minimum requirements of the protection devices

!
C A U T I O N
Ensure specifically that there is an Earth Leakage Breaker (ELB) installed for the units (outdoor and indoor unit).
If the installation is already equipped with an Earth Leakage Breaker (ELB), ensure that its rated current is large enough to hold the current of the
units (outdoor and indoor unit).
?
N O T E
Electric fuses can be used instead of magnetic Circuit Breakers (CB). In that case, select fuses with similar rated values as the CB.
The Earth Leakage Breaker (ELB) mentioned on this manual is also commonly known as Residual Current Device (RCD) or Residual Current
Circuit Breaker (RCCB).
The Circuit Breakers (CB) are also known as Thermal-Magnetic Circuit Breakers or just Magnetic Circuit Breakers (MCB).

Split system - Outdoor unit
Model
Power supply
RAS-2WHVNP
RAS-2.5WHVNP
RAS-3WHVNP
1~ 230V 50Hz
RAS-4WHVNPE
RAS-5WHVNPE
RAS-6WHVNPE
RAS-4WHNPE
RAS-5WHNPE
RAS-6WHNPE
3N~ 400V 50Hz
RAS-8WHNPE
RAS-10WHNPE
MC: Maximum current; CB: Circuit breaker; ELB: Earth leakage breaker
96
PMML0335A rev.1 - 04/2016
Operation mode
Without DHW tank heater
With DHW tank heater
Without DHW tank heater
With DHW tank heater
Without DHW tank heater
With DHW tank heater
Without DHW tank heater
With DHW tank heater
Without DHW tank heater
With DHW tank heater
Without DHW tank heater
50Hz
With DHW tank heater
Without DHW tank heater
With DHW tank heater
Applicable voltage
U max. (V)
253
440
Power supply
Max.
cables
current
(A)
EN60335-1
22
2 x 6.0 mm² + GND
34
2 x 10.0 mm² + GND
31
2 x 6.0 mm² + GND
43
2 x 10.0 mm² + GND
31
2 x 6.0 mm² + GND
43
2 x 10.0 mm² + GND
31
2 x 6.0 mm² + GND
43
2 x 10.0 mm² + GND
14
4 x 4.0 mm² + GND
27
4 x 6.0 mm² + GND
14
4 x 4.0 mm² + GND
27
4 x 6.0 mm² + GND
16
4 x 6.0 mm² + GND
29
4 x 10.0 mm² + GND
MC
(A)
U min. (V)
14
16
18
207
30
30
30
14
14
360
16
24
24
Transmitting
Actuator
cables
cables
EN60335-1
EN60335-1
2 x 0.75 mm
2
2 x 0.75 mm
2
+ GND
CB
ELB
(A)
(nº of poles/A/mA)
16
16
20
2/40/30
32
32
32
15
15
20
4/40/30
25
25