GENERAL DATA

3.3 GENERAL SPECIFICATIONS

3.3.1 Considerations

The sound data is based on the following conditions:
-
Outdoor ambient temperature (DB/WB): 7/6ºC.
-
Water inlet/outlet temperature: 47/55ºC (mark: *1); 30/35ºC (mark: *2).
-
Distance of the unit from the measuring point: At 1 meter from the unit's front surface; 1,5 meter from floor level.
-
The sound pressure level is measured in an anechoic chamber, so reflected sound should be taken into consideration when
installing the unit.
-
The sound power level is measured in a reverberant room, in accordance with the standard EN12102. Used environment
conditions are the same that specified in EN14511 for performance test.
The nominal water flow rate is calculated under the following conditions:
-
Outdoor ambient temperature (DB/WB): 7/6ºC.
-
Water inlet/outlet temperature: 47/55ºC (mark: *1); 30/35ºC (mark: *2).
Regarding data market with (mark: *3), it corresponds to the height of the unit with the minimum mounting foot height. This value
can be adjusted up to +30 mm.
For specific details about data corresponding to the working range, please refer to the chapter
Keywords:
DB: Dry bulb
WB: Wet bulb

3.3.2 Split system - Outdoor unit

Model
Power supply
Noise level (sound pressure) (*1)
Noise level (sound power)
Air flow
Cabinet colour
Dimensions (H x W x D)
Net weight
Gross weight
Piping diameter (liquid / gas)
Minimum piping length
Maximum chargeless piping length
Maximum piping length
(additional refrigerant charge needed)
Height difference between OU and IU
(higher OU / lower OU)
Working range (cooling // heating // DHW)
Refrigerant
Refrigerant charge before shipment
Compressor type
Blank data: To be informed later.
33
PMML0335A rev.1 - 04/2016
-
dB(A)
(*1)
dB(A)
(*2)
dB(A)
m
/min
3
-
mm
kg
kg
mm (inch)
Ø6.35 (1/4) / Ø12.7 (1/2)
m
m
m (g/m)
m
ºC (DB)
-
kg
-
RAS-2WHVNP
RAS-2.5WHVNP
1~ 230V 50Hz
61
59
40.6
Natural grey (1.0Y 8.5/0.5)
600 x 792 x 300
43
46
Ø6.35 (1/4) / Ø12.7 (1/2)
50(30)
10~46 // -15~25 / -15~35
1.4
Scroll DC Inverter driven
"4 WORKING
RANGE".
RAS-3WHVNP
63
64
60
61
40.6
44.7
43
44
46
49
Ø9.52 (3/8) / Ø15.88 (5/8)
5
15
50(40)
30 / 20
R410A
1.5
1.7